MAINTENANCE

6-7

HOT WATER

TUBE

COMPRESSION

FITTING

Figure 6.8

BTU Transmitter Shell Components

IMPELLER HOUSING

COVER

Figure 6.9

Impeller Housing Disassembly

19. Once the BTU transmitter has been inspected and cleaned, reassemble in the reverse order.

NOTE:

Do not attempt to adjust the Hydraulic Zero Needle Valve. This is a

factory-preset item. Refer to

Figure 6.5. If setting has been tampered

with or BTU transmitter is being replaced, see procedure in

Section

6.12, page 6-17.

NOTE:

Compression fittings are nickel-plated and should be replaced only with

nickel-plated fittings. Do not use brass fittings

.

6.8 MANIFOLD AND EXHAUST TUBES

The presence of even trace amounts of chlorides and/or sulfur, in the combustion air and fuel sources,

can lead to the formation of deposits on the inside of the exchanger tubes, the exhaust manifold, and/or

the condensate cup. The degree of deposition is influenced by the extent of the condensing operation and

the chloride and sulfur levels that vary significantly from application to application.