C-more control panel operation – AERCO C-More Controls User Manual
Page 24

C-MORE CONTROL PANEL OPERATION
Table 3-2. Default Settings – Continued
MENU & OPTION
FACTORY DEFAULT
Breakpoint At 100% (If Unit Type = Water Heater)
77°F
Breakpoint At 90% (If Unit Type = Water Heater)
81°F
Breakpoint At 80% (If Unit Type = Water Heater)
85°F
Breakpoint At 70% (If Unit Type = Water Heater)
91°F
Breakpoint At 60% (If Unit Type = Water Heater)
95°F
Breakpoint At 50% (If Unit Type = Water Heater)
102°F
Breakpoint At 40% (If Unit Type = Water Heater)
110°F
Breakpoint At 30% (If Unit Type = Water Heater)
112°F
Breakpoint At 20% (If Unit Type = Water Heater)
114°F
Breakpoint At 10% (If Unit Type = Water Heater)
130°F
Breakpoint At 0% (If Unit Type = Water Heater)
135°F
Reset Defaults?
No
Calibration Menu
Stepper Fbk
Cal 0%
PWM Adj
0.0%
Analog In Adj
0.0%
Flow In Adj
0.0%
CO In Adj
0.0%
O2 In Adj
0.0%
mA Out Adj
0.0 mA
A/F Sensitivity
2%
Power Reset
Auto
Water Temp Reset
Auto
Gas Press Reset
Manual
Min Off Time
1 Min (Boiler), 0 Min (Water Heater)
Heatr Tuning Dsp (If Unit Type = Water Heater)
Disabled
Heatr Bkpt Dsp (If Unit Type = Water Heater)
Disabled
Stop Level
16
Start Level
20
Diagnostics Menu
Display Test
Off
Keypad Test
Off
Relay Test
Off
Switch Test
Off
Stepper Test
0%
Sensor Log Int
30 min.
20