C-MORE CONTROL PANEL OPERATION


Table 2-2. Setup Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Passsword
Level 1 = 159
Level 2 = 6817

0 9999 0

Language English

English

Time

12:00 am

11:59 pm

Date 01/01/00

12/31/99

Unit of Temp

Fahrenheit

Celsius

Fahrenheit

Comm Address

0

127

0

Baud Rate

2400
4800
9600

19.2K

9600

Software

Ver 0.0

Ver 9.9




2.5 CONFIGURATION MENU

The Configuration Menu shown in Table 2-3
permits adjustment of the Internal Setpoint
(Setpt) temperature regardless of whether the
valid password has been entered. Setpt is
required for operation in the Constant Setpoint
mode. The remaining options in this menu
require the valid password to be entered, prior to
changing existing entries. This menu contains a
number of other configuration settings which
may or may not be displayed, depending on the
current operating mode setting.

NOTE:

The Configuration Menu settings shown in
Table 2-3 are Factory-Set in accordance
with the requirements specified for each
individual order. Therefore, under normal
operating conditions, no changes will be
required.

8