5 configuration menu, C-more control panel operation – AERCO C-More Controls User Manual
Page 12

C-MORE CONTROL PANEL OPERATION
Table 2-2. Setup Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Passsword
Level 1 = 159
Level 2 = 6817
0 9999 0
Language English
English
Time
12:00 am
11:59 pm
Date 01/01/00
12/31/99
Unit of Temp
Fahrenheit
Celsius
Fahrenheit
Comm Address
0
127
0
Baud Rate
2400
4800
9600
19.2K
9600
Software
Ver 0.0
Ver 9.9
2.5 CONFIGURATION MENU
The Configuration Menu shown in Table 2-3
permits adjustment of the Internal Setpoint
(Setpt) temperature regardless of whether the
valid password has been entered. Setpt is
required for operation in the Constant Setpoint
mode. The remaining options in this menu
require the valid password to be entered, prior to
changing existing entries. This menu contains a
number of other configuration settings which
may or may not be displayed, depending on the
current operating mode setting.
NOTE:
The Configuration Menu settings shown in
Table 2-3 are Factory-Set in accordance
with the requirements specified for each
individual order. Therefore, under normal
operating conditions, no changes will be
required.
8