C-MORE CONTROL PANEL OPERATION
Table 2-6. Diagnostics Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Display Test
Off
LEDs
7-Seg
Bar-graph
Off
Keypad Test
Off
Manual, Menu
Up, Down
Change, Enter
Clear
(Back Key exits test mode)
Off
Relay Test
(Allows user to force
outputs ON or OFF)
Off
Igniter ON/Igniter OFF
Blower ON/Blower OFF
Pump ON/Pump OFF
Aux ON/Aux OFF
Fault ON/Fault OFF
Off
Switch Test
(Allows user to view
the status of all
switch inputs)
Off
Exhaust sw ON/Exhaust sw OFF
SSOV sw ON/SSOV sw OFF
Blower Proof ON/Blower Proof OFF
Ignition sw ON/Ignition sw OFF
Over Temp sw ON/Over Temp sw OFF
Low Gas Pres ON/Low Gas Pres OFF
Hi Gas Pres ON/Hi Gas Pres OFF
Water Lev sw ON/Water Lev sw OFF
Rem Int sw ON/Rem Int sw OFF
Front Pnl sw ON/Front Pnl sw OFF
Delayed Int ON/Delayed Int OFF
Purge sw ON/Purge sw OFF
Off
Stepper Test
(Allows user to
adjust the stepper
motor position using
the
▲ and ▼ keys)
0% 100%
0%
Sensor Log Int
(Allows user to set
the time interval for
logging Sensor
inputs in Database)
Off
1 Min, 5 Min
15 Min, 30 Min
1 Hr, 6 Hrs
12 Hrs, or 24 Hrs
30 Min.
12