C-MORE CONTROL PANEL OPERATION
Table 3-2. Default Settings
MENU & OPTION
FACTORY DEFAULT
Setup Menu
Password
0
Language
English
Unit of Temp
Fahrenheit
Comm Address
0
Baud Rate
9600
Configuration Menu
Internal Setpt
130°F
Unit Type
Boiler
Unit Size
1.0 MBTU
Boiler Mode
(If Unit Type = Boiler)
Constant Setpoint
Heater Mode
(If Unit Type = Water Heater)
Constant Setpoint
Remote Signal
(If Mode = Remote Setpoint, Direct Drive or
Combination)
4 – 20 mA / 1-5V
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
70°F
Reset Ratio
(If Boiler Mode = Outdoor Reset)
1.2
Outdoor Sensor
Disabled
System Start Tmp
(If Outdoor Sensor = Enabled)
60°F
Temp Hi Limit
210°F
Max Fire Rate
100%
Pump Delay Timer (If Unit Type = Boiler)
0 min
Aux Start On Dly
0 sec
Failsafe Mode
Shutdown
mA Output
Off
Low Fire Timer
2 sec
Setpt Limiting
Disabled
Setpt Limit Band
5°F
Tuning Menu
Prop Band
70°F (Boiler), 8°F (Water Heater)
Integral Gain
1.00 (Boiler), 1.60 (Water Heater)
Derivative Time
0.00 min (Boiler), 0.10 min (Water Heater)
Min Load Adj (If Unit Type = Water Heater)
0°F
Max Load Adj (If Unit Type = Water Heater)
0°F
FFWD Temp Adj (If Unit Type = Water Heater)
N/A
Outlet Feedback (If Unit Type = Water Heater)
On
Feedback Gain (If Unit Type = Water Heater)
0.05