Page 77

background image

MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS

Installation, Operation & Maintenance Manual

3.37 Conversion From Natural Gas To Propane Gas

To convert the unit to use propane gas, instead of natural gas, do the following:

Converting From Natural Gas to Propane Gas

1. Set nominal heat by adjusting the fan speed parameter FH (FAN MAX) from the E8

controller as shown in Table 3-7, and Modulex EXT Pressure and CO

2

Level

Calibration in Table 3-6, above. This parameter requires a password to change.

2. Adjust CO

2

(%) minimum and maximum levels according to the type of gas as shown

in table below. See section 3.33, Burner Calibration for more information.

Gas Type

CO

2

Level (%) Minimum CO

2

Level (%) Maximum

Natural Gas

8.5

10

Propane Gas

10

11

3.

After gas conversion to propane and calibration, the gas installer should complete and
apply this label, or equivalent, as close to the rating label as possible:

Figure 3-42: MODULEX EXT Label