MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS
Installation, Operation & Maintenance Manual
Table 6-4: BMM Fault Codes (Continued)
CODE DESCRIPTION
EFFECT
CORRECTION
RESET
E 24
Fan speed out of 
control: It 
doesn't reach 
pre-purge speed 
within 30 
seconds. 
Ignition retry 
after 60 
second delay 
and failure 
remains until 
we have a 
successful 
burner 
operation. 
Check fan wiring.
AUTOMATIC/MANUAL
E 26
Fan speed out of 
control: It 
doesn't stop 
within 30 
seconds after 
turned OFF. 
Ignition is 
inhibited. 
Check fan wiring.
AUTOMATIC
E 27
Air flow failure 
during ignition. 
Restart pre-
purge timer. 
The failure 
remains until 
we have a 
successful 
burner 
operation. 
Check fan and wiring. 
Check air proving switch 
and wiring. 
AUTOMATIC
E 30
Settings 
corrupted. 
Ignition is 
inhibited. 
Pump runs for 
5 min at max 
speed. 
Re-program the settings. 
Contact factory. 
MANUAL - cycle the 
power or send reset 
message. 
E 32
Line voltage too 
low (<96 VAC). 
Wait for 
proper line 
voltage (>102 
VAC). 
Check input voltage. Try 
another BMM. 
AUTOMATIC
E 40
Low water flow. 
Low water flow 
switch activated. 
Burners 
turned OFF. 
Check water flow or 
check switch. 
AUTOMATIC
 
 
Page 120 of 148