beautypg.com

1 boiler room safety concerns, 2 products to avoid in the boiler room – AERCO Modulex EXT 321 - 1123 User Manual

Page 30

background image

MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS

Installation, Operation & Maintenance Manual

Figure 3-6: Boiler (Front View) on Housekeeping Pad with Condensate Drain Pipe

Boiler Room Safety Concerns

3.6.1

When selecting the position for the installation of the boiler please comply with the following
safety requirements:

Ensure easy access to the components of the boiler to facilitate maintenance.

The room where the boiler will be placed must always be frost free.

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this
or any other appliance.

Never use or store any chlorinated detergents or halogenated hydrocarbons (e.g. in
spraycans, solvents and detergents, paints, adhesives) in proximity to the boiler.

For outdoor installation see Warning for Outdoor installation on page 16.

Products to Avoid in the Boiler Room

3.6.2

Do NOT store the following products in the boiler room and/or around combustion air intake
vents.

Spray cans containing chlorocarbons/fluorocarbons

Ammonium and/or ammonium solutions

Permanent wave solutions

Chlorinated waxes and/or cleaners

Chlorinated swimming pool chemicals

Calcium chloride used for thawing

Sodium chloride used for water softening

Refrigerant leaks

Paint or varnish removers

Well or Trench

for Condensate

Drain Pipe

Condensate

Drain Pipe

Boiler Housekeeping
Pad (Support Base)

At Least
3.93” (100mm)

MODULEX EXT
Boiler Front

Page 30 of 148

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0087_0E

12/01/14

Phone: 800-526-0288

GF-143