MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS

Installation, Operation & Maintenance Manual

Table 3-6: Modulex EXT Pressure, CO

2

and O

2

Level Calibration Tables

EXT 321

Gas

Type

Supply

Pressure

Wc (kPa)

CO

2

Level

O

2

Level

Fan Speed

Ǿ Mixer

Injectors

Ǿ in.

(mm)

Min. Gas

Consumption

ft

3

/hr (m

3

/hr)

Max. Gas

Consumption

ft

3

/hr (m

3

/hr)

Start

Output

% IG

(%)

Min.

(%)

Max.

(%)

Min.

(%)

Max.

Min.

(FL)

Max.

(FH)

NOMINAL ALTITUDE

Natural

7 (1.74)

8.5

10

3.1

5.8

31

91

0.27 (7)

45 (1.29)

316 (8.95)

50

Propane

11 (2.74)

10

11

1.3

3.1

30

84

0.27 (7)

18 (0.50)

122 (3.46)

50

HIGH ALTITUDE

Natural

7 (1.74)

8.5

10

3.1

5.8

35

100

0.27 (7)

45 (1.29)

316 (8.95)

50

Propane

11 (2.74)

10.8 10.8

1.3

3.1

30

73

0.27 (7)

18 (0.50)

109 (3.11)

50

EXT 481

Gas

Type

Supply

Pressure

Wc (kPa)

CO

2

Level

O

2

Level

Fan Speed

Ǿ Mixer

Injectors

Ǿ in.

(mm)

Min. Gas

Consumption

ft

3

/hr (m

3

/hr)

Max. Gas

Consumption

ft

3

/hr (m

3

/hr)

Start

Output

% IG

(%)

Min.

(%)

Max.

(%)

Min.

(%)

Max.

Min.

(FL)

Max.

(FH)

NOMINAL ALTITUDE

Natural

7 (1.74)

7.5

10

3.1

5.8

31

91

0.27 (7)

45 (1.29)

474 (13.43)

50

Propane

11 (2.74)

10

11

1.3

3.1

30

84

0.27 (7)

18 (0.50)

183 (5.19)

50

HIGH ALTITUDE

Natural

7 (1.74)

8.5

10

3.1

5.8

35

100

0.27 (7)

45 (1.29)

474 (13.43)

50

Propane

11 (2.74)

10.8 10.8

1.3

3.1

30

73

0.27 (7)

18 (0.50)

164 (4.67)

50

EXT 641

Gas

Type

Supply

Pressure

Wc (kPa)

CO

2

Level

O

2

Level

Fan Speed

Ǿ Mixer

Injectors

Ǿ in.

(mm)

Min. Gas

Consumption

ft

3

/hr (m

3

/hr)

Max. Gas

Consumption

ft

3

/hr (m

3

/hr)

Start

Output

% IG

(%)

Min.

(%)

Max.

(%)

Min.

(%)

Max.

Min.

(FL)

Max.

(FH)

NOMINAL ALTITUDE

Natural

7 (1.74)

8.5

10

3.1

5.8

31

91

0.27 (7)

45 (1.29)

631 (17.87)

50

Propane

11 (2.74)

10

11

1.3

3.1

30

84

0.27 (7)

18 (0.50)

243 (6.88)

50

HIGH ALTITUDE

Natural

7 (1.74)

8.5

10

3.1

5.8

35

100

0.27 (7)

45 (1.29)

631 (17.87)

50

Propane

11 (2.74)

10.8 10.8

1.3

3.1

30

73

0.27 (7)

18 (0.50)

219 (6.23)

50

NOTE

Check the O

2

levels often, especially at low flow rates.

For high altitude installations, consult document number C302.6 (MLX EXT Alt Derate).

Page 72 of 148

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0087_0E

12/01/14

Phone: 800-526-0288

GF-143