MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS

Installation, Operation & Maintenance Manual

Table 3-6: Modulex EXT Pressure, CO

2

and O

2

Level Calibration Tables

EXT 802

Gas

Type

Supply

Pressure

Wc (kPa)

CO

2

Level

O

2

Level

Fan Speed

Ǿ Mixer

Injectors

Ǿ in.

(mm)

Min. Gas

Consumption

ft

3

/hr (m

3

/hr)

Max. Gas

Consumption

ft

3

/hr (m

3

/hr)

Start

Output

% IG

(%)

Min.

(%)

Max.

(%)

Min.

(%)

Max.

Min.

(FL)

Max.

(FH)

NOMINAL ALTITUDE

Natural

7 (1.74)

8.5

10

3.1

5.8

31

91

0.27 (7)

45 (1.29)

790 (22.39)

50

Propane

11 (2.74)

10

11

1.3

3.1

30

84

0.27 (7)

18 (0.50)

306 (8.65)

50

HIGH ALTITUDE

Natural

7 (1.74)

8.5

10

3.1

5.8

35

100

0.27 (7)

45 (1.29)

790 (22.39)

50

Propane

11 (2.74)

10.8 10.8

1.3

3.1

30

73

0.27 (7)

18 (0.50)

274 (7.79)

50

EXT 962

Gas

Type

Supply

Pressure

Wc (kPa)

CO

2

Level

O

2

Level

Fan Speed

Ǿ Mixer

Injectors

Ǿ in.

(mm)

Min. Gas

Consumption

ft

3

/hr (m

3

/hr)

Max. Gas

Consumption

ft

3

/hr (m

3

/hr)

Start

Output

% IG

(%)

Min.

(%)

Max.

(%)

Min.

(%)

Max.

Min.

(FL)

Max.

(FH)

NOMINAL ALTITUDE

Natural

7 (1.74)

8.5

10

3.1

5.8

31

91

0.27 (7)

45 (1.29)

948 (26.87)

50

Propane

11 (2.74)

10

11

1.3

3.1

30

84

0.27 (7)

18 (0.50)

367 (10.39)

50

HIGH ALTITUDE

Natural

7 (1.74)

8.5

10

3.1

5.8

35

100

0.27 (7)

45 (1.29)

948 (26.87)

50

Propane

11 (2.74)

10.8 10.8

1.3

3.1

30

73

0.27 (7)

18 (0.50)

329 (9.35)

50

EXT 1123

Gas

Type

Supply

Pressure

Wc (kPa)

CO

2

Level

O

2

Level

Fan Speed

Ǿ Mixer

Injectors

Ǿ in.

(mm)

Min. Gas

Consumption

ft

3

/hr (m

3

/hr)

Max. Gas

Consumption

ft

3

/hr (m

3

/hr)

Start

Output

% IG

(%)

Min.

(%)

Max.

(%)

Min.

(%)

Max.

Min.

(FL)

Max.

(FH)

NOMINAL ALTITUDE

Natural

7 (1.74)

8.5

10

3.1

5.8

31

91

0.27 (7)

45 (1.29)

1,106 (31.34)

50

Propane

11 (2.74)

10

11

1.3

3.1

30

84

0.27 (7)

18 (0.50)

428 (12.12)

50

HIGH ALTITUDE

Natural

7 (1.74)

8.5

10

3.1

5.8

35

100

0.27 (7)

45 (1.29)

1,106 (31.34)

50

Propane

11 (2.74)

10.8 10.8

1.3

3.1

30

73

0.27 (7)

18 (0.50)

384 (10.91)

50

NOTE

Check the O

2

levels often, especially at low flow rates.

For high altitude installations, consult document number C302.6 (MLX EXT Alt Derate).

OMM-0087_0E

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 73 of 148

GF-143

Phone: 800-526-0288