2 bcm (boiler communications module) fault codes – AERCO Modulex EXT 321 - 1123 User Manual
Page 117

MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS
Installation, Operation & Maintenance Manual
BCM (Boiler Communications Module) Fault Codes
6.1.2
The table below lists the fault codes and troubleshooting tips associated with the BCM.
Table 6-3: BCM Fault Codes
CODE
DESCRIPTION
EFFECT
CORRECTION
RESET
E 17
Boiler pipe is frozen. 
Flow sensor temp. is 
36°F or less. 
Ignition is 
inhibited. Pump 
runs for 5 min at 
max speed. 
Carefully 
defrost boiler. 
AUTOMATIC - when Flow 
sensor is greater than 41°F. 
E 18
Maximum Δ-
temperature protection. 
Flow temperature - 
Return Temperature > 
Water 
Δ-Temp
Protection + 50°F
All burners turned 
OFF and Pump 
ON at maximum 
speed. 
Check the 
system 
installation. 
AUTOMATIC -
when Δ-
temperature < Water Δ-
Temp Protection. 
E 19
High outlet 
temperature. Flow 
sensor temperature > 
203°F. 
All burners turned 
OFF and pump 
ON at maximum 
speed. 
Check Flow 
Sensor or 
system pump. 
AUTOMATIC - when Flow 
sensor < 176°F. 
E 37
BCM: Internal fault
E 38
Settings corrupted by 
electromagnetic 
interference. 
Ignition is 
inhibited. Pump 
runs for 5 min at 
max speed. 
Re-program 
the settings. 
Contact 
factory. 
MANUAL - push reset 
switch or cycle power. 
E 56
BCM: No remote 
control detected 
E 57
BCM: No BMM 
detected 
E 58
BCM: Sensor global 
flow detected. 
Ignition is 
inhibited. 
Close request 
input for 
manual 
operation. 
MANUAL - push reset 
switch or cycle power. 
 
 
 