beautypg.com

AERCO BMK 1000 User Manual

Page 91

background image

Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 7 – MAINTENANCE

OMM-0082_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 91 of 192

GF-130

Ph.: 800-526-0288

05/21/2014

Igniter-Injector Replacement

Continued

3. Disconnect the cable from the igniter-injector (

Figure 7-1

).

4. Refer to the partial exploded view in Figure 7-2. Using a 7/16” open-end wrench,

disconnect the compression nut securing the gas injector tube of the igniter-injector to the
elbow of the staged ignition assembly. Disconnect the staged ignition assembly from the
igniter-injector.

5. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end

wrench.

6. Check the igniter-injector for evidence of erosion or carbon build-up. If there is evidence

of substantial erosion or carbon build-up, the igniter-injector should be replaced. If carbon
build-up is present, clean the component using fine emery cloth. Repeated carbon build-
up is an indication that the combustion settings of the unit should be checked. Refer to
Chapter 4 for combustion calibration procedures.

Figure 7-2: Igniter-Injector & Flame Detector Mounting Details

7. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end

wrench.

8. Check the igniter-injector for evidence of erosion or carbon build-up. If there is evidence

of substantial erosion or carbon build-up, the igniter-injector should be replaced. If carbon
build-up is present, clean the component using fine emery cloth. Repeated carbon build-
up is an indication that the combustion settings of the unit should be checked. Refer to
Chapter 4 for combustion calibration procedures.

9. Prior to reinstalling the igniter-injector, a high temperature, conductive, anti-seize com-

pound must be applied to the threads.

NOTE

If a replacement igniter-injector (part no. 58023) is being installed, a
compression nut containing a built-in ferrule will be included with the
replacement part. If needed, 3 indexing washers are also included These
washers may be needed to properly position the gas injector tube of the
igniter-injector within the 120° angle range shown in Figure 7-3.

O2 SENSOR

& WASHERS

STAGED
IGNITION
SOLENOID

INJECTOR-IGNITOR

INDEXING WASHERS
(Quantity = 0-3 as
required)

FLAME

DETECTOR

& GASKET

COMPRESSION FITTING AND ELBOW

BURNER

PLATE

This manual is related to the following products: