Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 9 – RS-232 COMMUNICATION

OMM-0082_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 121 of 192

GF-130

Ph.: 800-526-0288

05/21/2014

NOTE

The Operation Time (T) Log can store thousands of records. Therefore,
to view the most recently logged record, enter “T” followed by 0 (zero)
and press Enter (i.e. T0 ). To view earlier records in reverse
chronological order, enter T and press Enter. To go back 200 or 1000
records, enter T200 or T1000, etc. and press Enter.

9.4.2 Operation Time Log

The Operation Time Log consists of a string of ASCII records stored in non-volatile memory
within the C-More Control Panel. Events such as power-up, ignition and turn-off are time
stamped. Data logged while the unit is running are run-length encoded. Data is logged or the
run-length incremented every 30 seconds. For a new run record to be logged, the fire rate or
flame strength must change by more than 5%, or the run mode must change. At steady-state,
the run-length is allowed to reach a maximum of 30 minutes before the record is logged. This
means that no more than 30 minutes of data can be lost if the unit loses power. Table 9-2
shows a sample Operation Time Log for a boiler:

The Operation Time Log can only be accessed through the RS-232 interface using a laptop or
other terminal device. Ten operation time records are displayed for each T command entry. The
operation time log can be cleared ONLY by factory authorized personnel using the Clear Log
option in the Factory menu.

Table 9-2: Sample Operation Time Log Display

Status

Fire Rate Flame Run Length

Date

Time

Off, Direct Drive

0

0

8

1/15/02

2:35pm

Run, Direct Drive

38

100

34

1/15/02

2:27pm

Run, Direct Drive

31

100

30

1/15/02

1:53am

Run, Direct Drive

35

100

2

1/15/02

1:23pm

Run, Direct Drive

29

100

0

1/15/02

1:21pm

Ignition

0

0

0

1/15/02

1:20pm

Off, Switch

0

0

35

1/15/02

12:30pm

Run, Manual

40

100

0

1/15/02

11:55am

Ignition

0

0

0

1/15/02

11:55am

Power-up

0

0

0

1/15/02

11:50am

NOTE

The Sensor (S) Log can store up to 1200 records. Therefore, to view the
most recently logged record, enter “S” followed by 0 (zero) and then
press Enter (i.e. S0 ). To view earlier records in reverse
chronological order, enter S and press Enter. To go back 200 or 700
records, enter S200 or S700, etc. and press Enter.