beautypg.com

AERCO BMK 1000 User Manual

Page 132

background image

Benchmark 750/1000 Boiler

CHAPTER 10. BOILER SEQUENCING TECHNOLOGY

Page 132 of 192

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0082_0J

05/21/2014

Ph.: 800-526-0288

GF-130

Option 5 – Continued



Step 3: Configure ALL C-More Units

On ALL Boilers:

1. Go to the Configuration Menu and set the BST Menu item to Enabled.
2. Go to the BST Menu and set the BST Mode item to BST Slave (for now) .

On MASTER only:

3. Go to the BST Setpoint item and enter the Failsafe Setpoint.

4. Go to the BST Setup Menu item and set to Enabled.
5. Go to the BST Setpoint Mode item and select Remote Setpoint.

6. Go to the Head Temp Source item and select FFWD Temp.

7. Go to the BST Remote Signal and select either 4-20ma or 0-20ma.

When ALL C-More units have been configured:

8. Go to the BST Menu of the desired Master unit and set the BST Mode item to BST

MASTER.

This manual is related to the following products: