Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

OMM-0082_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 45 of 192

GF-130

Ph.: 800-526-0288

05/21/2014

Table 3-4: Configuration Menu

*NOTE

The Bldg Ref Temp and Reset Ratio Menu Items are only
displayed when the Outdoor Sensor is set to “Enabled”.


Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Internal Setpt

Lo Temp Limit

Hi Temp Limit

130°F

Unit Type

KC Boiler, KC Boiler LN,

BMK Blr Std, BMK Blr Std Dual,

BMK Blr LN, BMK Blr LN Dual

KC Water Heater,

KC Water Heater LN,

Innovation WH

BMK Blr LN

Unit Size
(Only the unit sizes
available for the Unit
Type will be displayed)

750 MBH, 1000 MBH,

1500 MBH, 2000 MBH,
2500 MBH, 3000 MBH,

6000 MBH

750 MBH

or

1000 MBH

Fuel Type

Natural Gas, Propane

Natural Gas

Boiler Mode

Constant Setpoint,

Remote Setpoint,

Direct Drive,

Combination,

Outdoor Reset

Constant Setpoint

Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)

4 – 20 mA/1 – 5V

0 -20 mA/0 – 5V

PWM Input (Legacy BMS),

Network

4 – 20 mA,

1-5V

Outdoor Sensor

Enabled or Disabled

Disabled

*Bldg Ref Temp
(If Mode = Outdoor
Reset)

40°F

230°F

70°F

*Reset Ratio
(If Mode = Outdoor
Reset)

0.1

9.9

1.2

*System Start Tmp
(If Outdoor Sensor =
Enabled)

30°F

100°F

60°F

Setpt Lo Limit

40°F

Setpt Hi Limit

60°F

Setpt Hi Limit

Setpt Lo Limit

210°F

140°F

Temp Hi Limit

40°F

210°F

160°F