Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual

APPENDIX M – ULTRA-LOW NOx CALIBRATION

OMM-0082_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 187 of 192

GF-130

Ph.: 800-526-0288

05/21/2014

Ultra-Low NOx Natural Gas Combustion Calibration – Continued

NOTE

The remaining combustion calibration steps are performed using the
Combustion Cal Menu included in the C-More Control System. The combustion
calibration control functions will be used to adjust the oxygen level (%) at valve
positions of 80%, 60%, 45%, 30% and 18% as described in the following steps.
These steps assume that the inlet air temperature is within the range of 50°F to
100°F. If NOx readings exceed the target value of 9 ppm, increase the O

2

level

up to 1% higher than the listed calibration range. Record the increased O

2

value

on the Combustion Calibration sheet.

17.

Lower the valve position to 80% using the ▼arrow key.

18. Press the MENU key on the front panel of the C-MORE and access the Setup menu. Enter

password 6817 and then press the ENTER key.

19. Press the MENU key on the front panel of the C-MORE until Combustion Cal Menu

appears on the display.

20.

Press the ▲ arrow key until SET Valve Position appears on the display.

21. Press the CHANGE key. SET Valve Position will begin to flash.

22.

Press the ▲ arrow key until SET Valve Position reads 80%. Press the ENTER key.

23. Next, press the

down (▼) arrow key until CAL Voltage 80% is displayed.

24. Press the CHANGE key and observe that CAL Voltage 80% is flashing.

25. The oxygen level at the 80% valve position should be as shown below. Also, ensure that the

nitrogen oxide (NOx) and carbon monoxide (CO) readings do not exceed the following
values:

Ultra-Low NOx Combustion Calibration Readings

Valve Position

Oxygen (O

2

) %

Nitrogen Oxide

(NOx)

Carbon Monoxide

(CO)

80%

5% - 7%

<9 ppm

<100 ppm

26. If the oxygen level is not within the specified range,

adjust the level using the ▲ and ▼

arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the down ▼
arrow key decreases the oxygen level.

27. Once the oxygen level is within the specified range at 80%, press the ENTER key to store

the selected blower output voltage for the 80% valve position. Record all readings on the
Combustion Calibration Sheets provided.

28. Repeat steps 20 through 27 for valve positions of 60%, 45%, 30% and 18%* (see *NOTE

below). The oxygen (O

2

), nitrogen oxide (NOx) and carbon monoxide (CO) should remain

within the same limits for all valve positions as shown in the following table.

*NOTE

Set the Valve Position at 18% but make adjustments to the Combustion
Calibration value designated as 16%.