CHAPTER 6 – SAFETY DEVICE TESTING

OMM-0082_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 79 of 192

GF-130

Ph.: 800-526-0288

05/21/2014

6.3 HIGH GAS PRESSURE TEST

The instructions below apply to both the Natural Gas and Propane gas trains.

To simulate a high gas pressure fault, refer to Figure 6-1B and perform the following steps:

High Gas Pressure Test

1. Remove the 1/4“ plug from the leak detection ball valve at the High Gas Pressure switch,

shown in Figure 6-1B.

2. Install a 0 – 16” W.C. manometer (or W.C. gauge) where the 1/4” plug was removed.

3. Slowly open the leak detection ball valve near the High Gas Pressure switch.

4. Start the unit in Manual mode at a valve position (firing rate) between 25 and 30%.

5. With the unit running, monitor the gas pressure on the manometer installed in step 2 and

record the gas pressure reading.

6. Slowly increase the gas pressure using the adjustment screw on the SSOV (see Figure

4-3 in Chapter 4).

7. The unit should shut down and display a GAS PRESSURE fault message, and the

FAULT indicator should also start flashing at the following approximate pressures:

BMK 750 & 1000 – NATURAL GAS gas trains: 4.7” W.C.
BMK 750 – PROPANE gas train: 4.7” W.C.
BMK 1000 – PROPANE gas train: 10.5” W.C.

8. Reduce the gas pressure back to the value recorded in step 5. This pressure should be

within the range of

BMK 750 & 1000 – NATURAL GAS gas trains: 2.0” W.C. ± 0.4” W.C.
BMK 750 – PROPANE gas train: 3.9” W.C. ± 0.2” W.C.
BMK 1000 – PROPANE gas train: 7.4” W.C. ± 0.2” W.C.

9. Press the CLEAR button on the Control Box to clear the fault.

10. The fault message should clear and the FAULT indicator should go off. The unit should

restart.

11. Upon test completion, close the ball valve and remove the manometer. Replace the

1/4“plug removed in step 1.

Figure 6–1B: High Gas Pressure Test – Natural Gas gas train shown

SSOV

GAS INLET

TO AIR/FUEL

VALVE

HIGH GAS PRESSURE LEAK

DETECTION BALL VALVE

1/4” NTP PLUG
(Install manometer
here for High Gas
Pressure Test)

MANUAL SHUT-OFF

VALVE

HIGH GAS
PRESSURE SWITCH

LOW GAS
PRESSURE SWITCH