Appendix d – AERCO BMK 2.0 LN Nat. Gas for Mass. only User Manual
Page 82
APPENDIX D
Table D-3. Header Temperature for a Building Reference Temperature of 65F
RESET RATIO
Air
Temp
0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
65
65 65 65 65 65 65 65 65 65 65
60
68 69 70 71 72 73 74 75 76 77
55
71 73 75 77 79 81 83 85 87 89
50
74 77 80 83 86 89 92 95 98 101
45
77 81 85 89 93 97 101 105 109 113
40
80 85 90 95 100 105 110 115 120 125
35
83 89 95 101 107 113 119 125 131 137
30
86 93 100 107 114 121 128 135 142 149
25
89 97 105 113 121 129 137 145 153 161
20
92 101 110 119 128 137 146 155 164 173
15
95 105 115 125 135 145 155 165 175 185
10
98 109 120 131 142 153 164 175 186 197
5
101 113 125 137 149 161 173 185 197 209
0
104 117 130 143 156 169 182 195 208
-5
107 121 135 149 163 177 191 205 219
-10
110 125 140 155 170 185 200 215
-15
113 129 145 161 177 193 209
-20
116 133 150 167 201 218
Table D-4. Header Temperature for a Building Reference Temperature of 70F
RESET RATIO
Air
Temp
0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
70F
70 70 70 70 70 70 70 70 70 70
65F
73 74 75 76 77 78 79 80 81 82
60F
76 78 80 82 84 86 88 90 92 94
55F
79 82 85 88 91 94 97 100 103 106
50F
82 86 90 94 98 102 106 110 114 118
45F
85 90 95 100 105 110 115 120 125 130
40F
88 94 100 106 112 118 124 130 136 142
35F
91 98 105 112 119 126 133 140 147 154
30F
94 102 110 118 126 134 142 150 158 166
25F
97 106 115 124 133 142 151 160 169 178
20F
100 110 120 130 140 150 160 170 180 190
15F
103 114 125 136 147 158 169 180 191 202
10F
106 118 130 142 154 166 178 190 202 214
5F
109 122 135 148 161 174 187 200 213
0F
112 126 140 154 168 182 196 210
-5F
115 130 145 160 175 190 205
-10F
118 134 150 166 182 198 214
-15F
121 138 155 172 189 206
-20F
124 142 160 178 196 214
D-2