beautypg.com

Control panel operating procedures – AERCO BMK 2.0 LN Nat. Gas for Mass. only User Manual

Page 25

background image

CONTROL PANEL OPERATING PROCEDURES

3-3

Table 3-1 Operating Controls, Indicators and Displays – Continued

ITEM

NO.

CONTROL, INDICATOR

OR DISPLAY

FUNCTION

10

MENU Keypad

Consists of 6 keys which provide the following functions for
the Control Panel Menus:

MENU

Steps through the main menu categories shown in Figure 3-
2. The Menu categories wrap around in the order shown.

BACK

Allows you to go back to the previous menu level without
changing any information. Continuously pressing this key
will bring you back to the default status display in the VFD.
Also, this key allows you to go back to the top of a main
menu category.

▲ (UP) Arrow

When in one of the main menu categories (Figure 3-2),
pressing the ▲ arrow key will select the displayed menu
category. If the CHANGE key was pressed and the menu
item is flashing, pressing the ▲ arrow key will increment the
selected setting.

▼ (DOWN) Arrow

When in one of the main menu categories (Figure 3-2),
pressing this key will select the displayed menu category. If
the CHANGE key was pressed and the menu item is
flashing, pressing the ▼ arrow key will decrement the
selected setting.

CHANGE

Permits a setting to be changed (edited). When the
CHANGE

key is pressed, the displayed menu item will begin

to flash. Pressing the ▲ or ▼ arrow key when the item is
flashing will increment or decrement the displayed setting.

ENTER

Saves the modified menu settings in memory. The display
will stop flashing.

11

AUTO/MAN

Switch

This switch toggles the boiler between the Automatic and
Manual modes of operation. When in the Manual (MAN)
mode, the front panel controls are enabled and the
MANUAL

status LED lights.

When in the Automatic (AUTO) mode, the MANUAL status
LED will be off and the front panel controls disabled.

12

FIRE RATE

Bargraph

20 segment red LED bargraph continuously shows the Fire
Rate in 5% increments from 0 to 100%