beautypg.com

Troubleshooting – AERCO BMK 2.0 LN Nat. Gas for Mass. only User Manual

Page 63

background image

TROUBLESHOOTING

TABLE 8-1. BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

TROUBLESHOOTING/CORRECTIVE ACTION

PRG SWTCH OPEN

DURING PURGE

1. Defective purge switch.


2. No voltage present at switch.

3. Switch wired incorrectly.

4. Defective Power Supply Board or

fuse

5. Defective IGST Board

1. If the air-fuel valve does rotate, check the purge switch for

continuity when closing. Replace switch if continuity does not
exist.

2. Measure for 24 VAC from each side of the switch to ground. If

24VAC is not present, refer fault to qualified service personnel.

3. Check to ensure that the switch is wired correctly (correct wire

numbers on the normally open terminals).

4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not

steady ON, replace Power Supply Board.

5. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF

every second. If not, replace IGST Board.

OUTDOOR TEMP

SENSOR FAULT

1. Loose or broken wiring.

2. Defective Sensor.

3. Incorrect Sensor.

1. Inspect Outdoor Temperature sensor for loose or broken wiring.

2. Check resistance of sensor to determine if it is within

specification.

3. Ensure that the correct sensor is installed.

REMOTE SETPT

SIGNAL FAULT

1. Remote setpoint signal not present:

Not yet installed.
Wrong polarity.
Signal defective at source.
Broken or loose wiring.

2. Signal is not isolated (floating) if 4 to

20 mA.

3. Control Box signal type selection

switches not set for correct signal
type (voltage or current).

1. Check I/O Box to ensure signal is hooked up.

Hook up if not installed.
If installed, check polarity.
Measure signal level.
Check continuity of wiring between source and boiler.

2. Check signal at source to ensure it is isolated.

3. Check DIP switch on PMC board to ensure it is set correctly for

the type of signal being sent. Check control signal type set in
Configuration Menu.

RESIDUAL

FLAME

1. SSOV not fully closed.

1. Check open/close indicator window of Safety Shut-Off Valve

(SSOV) and ensure that the SSOV is fully closed. If not fully
closed, replace the valve and or actuator.

Close gas shut-off valve downstream of SSOV. Install a
manometer or gauge in a gas test port between the SSOV and
the gas shut off valve. If a gas pressure reading is observed
replace the SSOV valve and or actuator.

8-9