beautypg.com

Troubleshooting – AERCO BMK 2.0 LN Nat. Gas for Mass. only User Manual

Page 65

background image

TROUBLESHOOTING


8.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES

Refer to Table 8-2 to troubleshoot faults which may occur without a specific fault message being displayed.

TABLE 8-2. BOILER TROUBLESHOOTING WITH NO FAULT MESSAGE DISPLAYED

OBSERVED INCIDENT

PROBABLE CAUSES

TROUBLESHOOTING/CORRECTIVE ACTION

Hard Light-Off

1. Staged Ignition Ball Valve closed.

2. Clogged/damaged Gas Injector

(Figure 8-2).

3. Defective Staged Ignition Solenoid

(Figure 8-2)

1. Open the 1/4” Ball Valve downstream of the SSOV (Fig. 8-1).

2. Remove and inspect Gas Injector to ensure it is not clogged or

damaged.

3. Close the 2” and the 1/4” Ball Valve downstream of the SSOV

(Fig. 8-1). Start the unit and listen for a “clicking” sound that the
Staged Ignition Solenoid makes during Ignition Trial. If “clicking”
sound is not heard after 2 or 3 attempts, replace the Staged
Ignition Solenoid.

Fluctuating Gas Pressure

1. Gas pressure going into unit is

fluctuating.

2. Damping Orifice not installed.

1. Stabilize gas pressure going into unit. If necessary, troubleshoot

Building Supply Regulator.

2. Check to ensure that the Damping Orifice is installed in the

SSOV Droop Eliminator (Figure 8-3).

Air/Fuel Valve “hunting” at 80%

Firing Rate

1. IGST and Power Supply Boards in

Control Box are outdated.

1. Check to ensure that the IGST and Power Supply Boards are

Rev. E or higher.






8-11