Troubleshooting – AERCO BMK 2.0 LN Nat. Gas for Mass. only User Manual

Page 69

background image

TROUBLESHOOTING

16. Shut down VFD power.

17. Turn On VFD power.

18. Set Pr. 59 to 1

19. Recalibrate the boiler using the combustion calibration procedures in Chapter 4.




Table 8-5. VFD Faults

NOTE

Check parameters 55, 56, 57, & 58 for the last 4 Trips.

VFD Fault

Possible Cause

U U

Low AC supply voltage

OU

High AC supply voltage

O.ht2

High ambient temperature

CL1

Analog input loss
(4-20 mA Air/Fuel Valve position signal)

EEF

Possible loss of parameters values

C.dAt

Empty SmartStick has been read

C.Err

Bad connection or faulty SmartStick

C.Acc

Bad connection or faulty SmartStick