Troubleshooting – AERCO BMK 2.0 LN Nat. Gas for Mass. only User Manual

Page 68

background image

TROUBLESHOOTING

Table 8-4. VFD Parameter Settings

VFD Parameter

Parameter Value

1 0.0
2 100.0
5

AI.AV

10 L3
19

Between -70.0 & 100.0

59 1
61

Between -150 & 250

62

Between 200 & 500

63

Between 250 & 600

64

Between 250 & 700

65

Between 400 & 850

71 18.20
72 18.21
73 18.22
74 18.23
75 18.24

• If a parameter value differs from the one shown in Table 8-4, reset the parameter to the value
shown in the Table.
• If a parameter value differs from the one shown in Table 8-4, reset the parameter to the value
shown in the Table

• If a parameter value differs from the one shown in Table 8-4, reset the parameter to the value

shown in Table 8-4, reset the parameter to the value shown in the Table.

• If parameters 61, 62, 63, 64, and 65 are skipped and do not appear, perform the following

procedure:

1. Set Pr. 28 to USA

2. Set Pr. 1 to 0.0

3. Set Pr. 2 to 100.0

4. Set Pr. 10 to L3

5. Set Pr. 19 to 82.0

6. Set Pr. 71 to 18.20

7. Set Pr. 72 to 18.21

8. Set Pr. 73 to 18.22

9. Set Pr. 74 to 18.23

10. Set Pr. 75 to 18.24

11. Set Pr. 61 to 50

12. Set Pr. 62 to 300

13. Set Pr. 63 to 400

14. Set Pr. 64 to 450

15. Set Pr. 65 to 600

8-14