Troubleshooting – AERCO BMK 2.0 LN Nat. Gas for Mass. only User Manual
Page 68
TROUBLESHOOTING
Table 8-4. VFD Parameter Settings
VFD Parameter
Parameter Value
1 0.0
2 100.0
5
AI.AV
10 L3
19
Between -70.0 & 100.0
59 1
61
Between -150 & 250
62
Between 200 & 500
63
Between 250 & 600
64
Between 250 & 700
65
Between 400 & 850
71 18.20
72 18.21
73 18.22
74 18.23
75 18.24
• If a parameter value differs from the one shown in Table 8-4, reset the parameter to the value
shown in the Table.
• If a parameter value differs from the one shown in Table 8-4, reset the parameter to the value
shown in the Table
• If a parameter value differs from the one shown in Table 8-4, reset the parameter to the value
shown in Table 8-4, reset the parameter to the value shown in the Table.
• If parameters 61, 62, 63, 64, and 65 are skipped and do not appear, perform the following
procedure:
1. Set Pr. 28 to USA
2. Set Pr. 1 to 0.0
3. Set Pr. 2 to 100.0
4. Set Pr. 10 to L3
5. Set Pr. 19 to 82.0
6. Set Pr. 71 to 18.20
7. Set Pr. 72 to 18.21
8. Set Pr. 73 to 18.22
9. Set Pr. 74 to 18.23
10. Set Pr. 75 to 18.24
11. Set Pr. 61 to 50
12. Set Pr. 62 to 300
13. Set Pr. 63 to 400
14. Set Pr. 64 to 450
15. Set Pr. 65 to 600
8-14