Safety device testing – AERCO BMK 2.0 LN Nat. Gas for Mass. only User Manual
Page 48
SAFETY DEVICE TESTING
4. Set
the
ON/OFF switch to the ON position to
start the unit.
5. The unit should shut down after reaching the
Ignition cycle and display FLAME LOSS
DURING IGN.
6. Open the valve previously closed in step 3
and press the CLEAR button.
7. Restart the unit and allow it to prove flame.
8. Once flame is proven, close the manual gas
valve located between the SSOV and the
Air/Fuel Valve.
9. The unit should shut down and display
FLAME LOSS DURING RUN.
10. Open the valve previously closed in step 8.
11. Press the CLEAR button. The unit should
restart and fire.
Figure 6-3
Manual Gas Shut-Off Valve Location
6.8 AIR FLOW FAULT TESTS
These tests check the operation of the Blower
Proof Switch and Blocked Inlet Switch shown in
Figure 6-3.
1. Start the unit in the Manual Mode at a firing
rate between 25% and 30%.
2. Once the unit has proved flame, remove the
memory stick from the Variable Frequency
Drive (VFD) shown in Figure 6-2.
3. The Blower Proof Switch will open and the
blower should stop. The unit should shut
down and display AIRFLOW FAULT
DURING RUN.
4. Replace the memory stick in the VFD.
5.
Press
the
CLEAR button. The unit should
restart.
6. Next, check the Blocked Inlet Switch by
closing the Iris Air Damper (Figure 4-4) to
position 8.
7. .The unit should shut down and again
display AIRFLOW FAULT DURING RUN.
8. Return the Iris Air Damper to its previous
setting.
9. Press the CLEAR button. The unit should
restart.
6.9 SSOV PROOF OF CLOSURE SWITCH
The SSOV shown in Figure 6-1 contains the
proof of closure switch. The proof of closure
switch circuit is checked as follows:
1. Set the unit’s ON/OFF switch to the OFF
position.
2. Place the unit in Manual Mode and set the
firing rate between 25% and 30%
3. Refer to Figure 6-1 and locate the SSOV.
4. Remove the cover from the SSOV by
loosening the screw shown in Figure 6-4. Lift
off the cover to access the terminal wiring
connections.
5. Disconnect wire #148 from the SSOV to
“open” the proof of closure switch circuit.
6. The unit should fault and display SSOV
SWITCH OPEN.
7. Replace wire #148 and press the CLEAR
button.
8. Set
the
ON/OFF switch to ON to start the
unit.
9. Remove the wire again when the unit
reaches the purge cycle and PURGING is
displayed.
10. The unit should shut down and display
SSOV FAULT DURING PURGE.
11. Replace the wire on the SSOV and press
the CLEAR button. The unit should restart.
6-4