process. Each analog option board can be identified by its serial number, which is entered in the
unit during the calibration process.
Table 4-1: Analog Output Calibration Parameters
Parameter
Setting
Displayed
Name
Description
Type/choices (*=Default)
P61200
10oFF
Value required to precisely output 0V in 0 –
10V output mode (i.e. offset).
Numeric Entry:
0 to 15,000
2,923*
P61201
10Gn
Value required to precisely output 10V in 0 –
10V output mode (i.e. gain).
Numeric Entry:
50,000 to 65,535
61,027*
P61202
0oFF
Value required to precisely output 0 mA in 0 –
20 mA output mode (i.e. offset).
Not adjustable:
0*
P61203
0Gn
Value required to precisely output 20 mA in 0 –
20mA output mode (i.e. gain).
Numeric Entry:
50,000 to 65,535
54,555*
P61204
4oFF
Value required to precisely output 0 mA in 4 –
20 mA output mode (i.e. offset).
Numeric Entry:
0 to 15,000
10,910*
P61205
4Gn
Value required to precisely output 20 mA in 4 –
20mA output mode (i.e. gain).
Numeric Entry:
50,000 to 65,535
54,555*
P61206
Srln
Analog option board serial number.
Numeric Entry:
0* - 4,294,967,295
Entering Calibration Values
Analog calibration values can be entered into the Model 370 and Model 375 by keying in the data
in the left-hand column, beginning at the line starting with "61200…", replacing the "%s" character
pairs with the [SELECT] key and "%e" with the [TARE] (370) or [SAMPLE] (375) key. The line
with the "%c" is not adjustable and cannot be entered.
You can adjust the included factory recommended offset and gain values to precisely configure
the system being connected to these outputs. Once the initial factory values have been entered,
pressing the [TARE] (370) or [SAMPLE] (375) key will cause the count value to increase one
count, and pressing the [PRINT] + [UNITS] keys will decrement the count value by one count. All
changes made are updated "live" to aid in calibrating a specific device to the analog option board
output. Holding down the key(s) will repeat the increment/decrement action.
Printout Example
100%s23640%e
Access Setup Modes, Allowing Changes
60100%s%e
P60100. c2004-GSE-
60101%s%e
P60101. 0Model 370 370p27132
60102%s%e
P60102. 09-02-2005
60200%s%e
P60200. BrdSn 420679
60201%s%e
P60201. AuditTrail Euro 00001
60202%s%e
P60202. InsSn102245
60203%s%e
P60203. AuditTrail Cal. 00025
60204%s%e
P60204. AuditTrail Setup 00050
61200%s2923%e
P61200. 10off 2923
61201%s61027%e
P61201. 10 Gn 61027
61202%s0%c
P61202. 0 off 0
61203%s54555%e
P61203. 0 Gn 54555
61204%s10910%e
P61204. 4 off 10910
61205%s54555%e
P61205. 4 Gn 54555
61206%s123456%e
P61206. Srl n 123456
%z Exit Setup Mode