Carrier 38AH044-084 User Manual
Page 48

Table 19A — One 2-Stage Thermostat Capacity
Control for 38AH044-084 Dual-Circuit Units
UNIT
38AH
QUANTITY OF LOADED
COMPRESSOR CYLINDERS
SYSTEM
CAPACITY
(%)
Circuit
A
Circuit
B
Total
044
4
4
8
100
2
4
6
75
4
0
4
50
2
0
2
25
054
4
6
10
100
2
6
8
79
2
4
6*
59
4
0
4
42
2
0
2
21
064
6
6
12
100
4
6
10
84
2
6
8*
68
6
0
6
48
4
0
4
32
2
0
2*
16
074
6
6
12
100
4
6
10
86
2
6
8*
72
6
0
6
43
4
0
4
29
2
0
2*
15
084
6
6
12
100
4
6
10
83
2
6
8*
66
6
0
6
50
4
0
4
33
2
0
2*
17
*Requires units with VAV (variable air volume) factory-supplied
option.
NOTE: Units have 2 independent refrigeration circuits. Circuit A is lead
circuit.
Table 19B — One 2-Stage Thermostat Capacity
Control for 38AH044-084 Optional Single-Circuit Units
UNIT
38AH
QUANTITY OF
LOADED CYLINDERS
SYSTEM
CAPACITY
(%)
044
8
100
6
75
4
50
2
25
054
10
100
8
81
6
60
6
56
4
37
2*
19*
064
12
100
10
82
8
64
6
56
4
36
2†
18
074
12
100
10
81
8
62
6
57
4
38
2†
19
084
12
100
10
83
8
66
6
50
4
33
2†
17
*Requires accessory unloader on lead 06E-265 compressor (A1).
†Requires VAV (variable air volume) factory-installed option or ac-
cessory unloader.
Table 20 — One 2-Stage Thermostat Capacity
Control for 38AH094-134 Units
UNIT
38AH
QUANTITY OF LOADED
COMPRESSOR CYLINDERS
SYSTEM
CAPACITY
(%)
Ckt A
Ckt B
Total
10
6
16
100
10
4
14
85
10
2
12
70*
10
0
10
55
094
8
0
8
44
6
0
6
33
4
0
4
22
104
10
12
22
100
8
12
20
91
8
10
18
82
10
6
16
73
6
6
12
55
6
4
10
45
0
6
6
27
4
0
4
18
0
4
4
18
2†
0
2
9†
124
12
12
24
100
10
12
22
92
10
10
20
83
8*
10
18
75*
6
10
16
67
6
8*
14
58*
6
6
12
50
4
6
10
42
6
0
6
25
4
0
4
17
2*
0
2
8*
134
12
12
24
100
10
12
22
92
10
10
20
83
8*
10
18
75*
6
10
16
67
6
8*
14
58*
6
6
12
50
4
6
10
42
6
0
6
25
4
0
4
17
2*
0
2
8*
*Requires VAV (variable air volume) unit or accessory unloader(s) field
installed on circuit lead compressor. Lead compressor is identified in
Table 16, page 40.
†Requires field-installed accessory unloader on circuit lead compres-
sor. Lead compressor is identified in Table 16, page 40.
NOTES:
1. Temperatures calculated with the minimum number of fans oper-
ating per circuit.
2. See Table 16, page 40, for information on lead and lag circuits.
CONTROL SET POINT — Control set point (cylinder load
point) is adjustable from 0 to 85 psig (0 to 586 kPag).
To adjust the set point, turn the control set point adjust-
ment nut clockwise to bottom stop. (See Fig. 46.) In this
position, load-up set point is 85 psig (586 kPag). Turn
adjustment counterclockwise to desired control set point.
Every full turn clockwise decreases the load-up set point by
7.5 psig (52 kPag).
PRESSURE DIFFERENTIAL — Pressure differential
(difference between cylinder load and unload points) is
adjustable from 6 to 22 psig (41 to 152 kPag). To adjust,
turn pressure differential adjustment screw counterclock-
wise to back stop position. The differential pressure is now
adjusted to 6 psig (41 kPag). Turn the adjustment screw clock-
wise to adjust the differential pressure. Every full clockwise
turn increases the differential by 1.5 psig (10 kPag).
48