beautypg.com

Carrier 38AH044-084 User Manual

Page 26

background image

Table 12 — Electrical Data — 50/60 Hz (Units 38AH124, 134)

UNIT

38AH

MODULE

VOLTAGE

DESIGNATION

COMPRESSOR

A1/A2

MODEL NO.

NAMEPLATE

V-Ph-Hz

SUPPLY

VOLTAGE*

MCA

MOCP

ICF

COMPRESSOR†

A1

A2

Min

Max

RLA

LRA

RLA

LRA

124A
124B
134A

500

06E8275/

265

208/230-3-60

187

254

249.3

350

617.5

106.4

506

89.7

446

600

460-3-60

414

508

115.5

150

307.6

46.8

253

43.6

223

100

575-3-60

518

632

100.6

125

226.1

40.4

176

36.5

164

200

380-3-60

342

418

126.9

175

341.1

52.6

280

45.5

247

900

380/415-3-50

342

440

115.7

150

335.6

46.8

280

43.6

223

300 (PW)

346-3-50

325

367

129.8

175

230.5

53.8

168

44.9

148

134B

500

06E8299/

275

208/230-3-60

187

254

330.5

450

829.0

147.4

690

106.4

506

600

460-3-60

414

508

148.6

200

408.2

65.4

345

46.8

253

100

575-3-60

518

632

132.2

175

336.8

57.1

276

40.4

176

200

380-3-60

342

418

174.5

250

458.0

78.8

382

52.6

280

900

380/415-3-50

342

440

149.0

200

403.8

65.4

345

46.8

280

300 (PW)

346-3-50

325

367

170.8

250

300.4

79.5

229

53.8

168

LEGEND

FLA

Full Load Amps

ICF

Maximum Instantaneous Current Flow During Starting.

(The point in the starting sequence where the sum of
the LRA for the starting compressors, plus the total RLA
for all running compressors, plus the FLA for all running
fan motors is maximum.)

kcmil

Thousand Circular Mils

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (used for sizing; complies with

National Electrical Code [NEC] [U.S.A. Standard],
section 430-24).

MOCP — Maximum Overcurrent Protection (used for sizing

disconnect; complies with NEC [U.S.A. Standard],
section 440- 22).

PW

Part Wind

RLA

Rated Load Amps

*Units are suitable for use on electrical systems where voltage sup-

plied to unit terminals is within listed minimum to maximum limits.

†All compressors are across-the-line start only except 346-v, 3-ph,

50 Hz unit.

NOTES:
1. Maximum allowable phase imbalance: voltage - 2%; amps - 10%.
2. Maximum incoming wire size for terminal block is 500 kcmil.

Table 13 — Control Circuit Electrical Data — 50/60 Hz

UNIT

DESIGNATION

UNIT POWER

CONTROL POWER

AMPS

V-Ph-Hz

V-Ph-Hz

Min

Max

−500

208/230-3-60

115-1-60

103

127

4.1

−600

460-3-60

115-1-60

103

127

4.1

−100

575-3-60

115-1-60

103

127

4.1

−200

380-3-60

230-1-60

207

253

2.0

−800

230-3-50

230-1-50

207

253

2.0

−900

380/415-3-50

230-1-50

207

253

2.0

−300

346-3-50

200-1-50

180

220

2.4

NOTE: Units 38AH124 and 134 have 2 control boxes per unit, one in each module.

26