beautypg.com

Carrier 38AH044-084 User Manual

Page 29

background image

LEGEND

AWG

American Wire Gage

CR

Control Relay

HD

Heating Device

IFC

Indoor-Fan Contactor

IFR

Indoor-Fan Relay

kcmil — Thousand Circular Mils
LLS

Liquid Line Solenoid

NEC

National Electrical Code

(U.S.A. Standard)

R

Heating Relay (field-

supplied 24-v sealed coil,
10 va maximum rating)

RV

Reversing Valve

TB

Terminal Block

Factory Wiring
Field Wiring

*To control heating device and provide automatic indoor-

fan operation on heating.

†Jumper removed only when separate 24-v trans-

former power source is used to power the 33CSUCE-06
relay pack.

**Field-supplied.

NOTES:

1. Liquid line solenoid valves LLS-A1 and A2 are used

for solenoid drops.

2. Solenoid drop is a safety feature which prevents

refrigerant migration to the compressor during
the OFF cycle. It is recommended on all systems
and required on systems where piping exceeds
75 ft (22.9 m) in length.

3. The 33CSUCE-01 relay pack requires 10 va.
4. Factory wiring is in accordance with NEC; field modi-

fications or additions must be in compliance with
all applicable codes.

5. Wiring for field power supply must be rated 75 C

minimum. Use copper, copper-clad aluminum, or
aluminum conductors. Maximum incoming wire size
for each terminal block is 500 kcmil.

6. Terminal blocks are for external field control con-

nections. Control connections are to be Class 1
wiring.

7. Field-supplied components (IFC, LLS-A1, and

LLS-A2) must have a maximum sealed coil rating
of 30 va each (0.25 amp at 120 vac and 0.13 amp

Fig. 21 — Field Wiring, One 2-Stage Thermostat — 38AH044-084 Optional Single-Circuit Units

Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac.

at 230 vac). Thermostats must have a minimum pilot
duty rating of 300 va (2.5 amps at 120 vac and
1.3 amps at 230 vac).

8. Replacement of factory wires must be with type

105 C wire or its equivalent.

9. Field-supplied liquid line solenoid valves installed at

the evaporator are required on all units.

10. Units have 175 va of power available for field-

installed accessories.

11. To minimize voltage drop, the following wire sizes are

recommended:

LENGTH —

Ft (M)

INSULATED WIRE — AWG

(35 C Minimum)

Up to 50
(15.2)

No. 18

50-75
(15.2-22.9)

No. 16

More Than 75
(22.9)

No. 14

29