beautypg.com

Carrier 38AH044-084 User Manual

Page 18

background image

Table 8A — Refrigerant Piping Requirements for 38AH044-084

Optional Single-Circuit Units and 38AH124,134

Modular Units (Dual-Circuit) — 60 Hz

UNIT

38AH

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)

15-20

(4.6-6.1)

20-50

(6.1-15.2)

50-75

(15.2-22.9)

75-100

(22.9-30.5)

100-150

(30.5-45.7)

150-200

(45.7-61.0)

L

S

L

S

L

S

L

S

L

S

L

S

044

7

8

2

1

8

7

8

2

1

8

1

1

8

2

1

8

1

1

8

2

5

8

*

1

3

8

2

5

8

*

1

3

8

3

1

8

*

054

7

8

2

1

8

1

1

8

2

5

8

1

1

8

2

5

8

1

1

8

2

5

8

1

3

8

3

1

8

*

1

3

8

3

1

8

*

064;

Modules 124A,

124B,134A

1

1

8

2

1

8

1

1

8

2

5

8

1

1

8

2

5

8

1

3

8

3

1

8

*

1

3

8

3

1

8

*

1

3

8

3

1

8

*

074;

Module 134B

1

1

8

2

1

8

1

1

8

2

5

8

1

3

8

3

1

8

1

3

8

3

1

8

1

3

8

3

1

8

1

5

8

3

5

8

*

084

1

1

8

2

5

8

1

1

8

2

5

8

1

3

8

3

1

8

1

3

8

3

1

8

1

5

8

3

5

8

1

5

8

3

5

8

*

LEGEND

CV

Constant Volume

L

Liquid Line

S

Suction Line

VAV — Variable Air Volume

*Double suction riser required on all units configurations if condens-

ing unit is elevated above evaporator.

†Double suction riser required on units with factory installed VAV op-

tion or CV units with additional field installed unloader on circuit A1
(lead) compressor if condensing unit is elevated above evaporator.

NOTES:
1. Addition of field-installed unloaders on A2 (lag) compressor is not

recommended.

2. Piping sizes are based on unit operation above 40 F (4.4 C) satu-

rated suction temperature (SST). When operating below 40 F
(4.4 C), refer to Carrier System Design Manual, E20-II

piping

design program, or ASHRAE Handbook to select proper line sizes.

3. Pipe sizes are based on the total linear length shown for each

column, plus a 50% allowance for fittings.

4. Suction and liquid line sizing is based on pressure drop equivalent

to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop

design criteria may allow selection of smaller pipe sizes, but at a
penalty of decreased system capacity and efficiency.

5. Double suction risers may be required if condensing unit is

elevated above the evaporator. See footnotes and double suction
riser table below.

6. Refer to Carrier System Design Manual, E20-II design program,

or ASHRAE Handbook for further information on selecting pipe
sizes for split systems.

7. All pipe sizes are OD inches. Equivalent sizes in millimeters

follow:

in.

mm

7

8

22.2

1

1

8

28.6

1

3

8

34.9

1

5

8

41.3

2

1

8

54.0

2

5

8

66.7

3

1

8

79.4

3

5

8

92.1

Table 8B — Refrigerant Piping Requirements for Double Suction Risers,

38AH044-084 Optional Single-Circuit Units and 38AH124,134

Modular Units (Dual-Circuit) — 60 Hz

UNIT

38AH

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT

15-50

(4.6-15.2)

50-75

(15.2-22.9)

75-100

(22.9-30.5)

100-150

(30.5-45.7)

150-200

(45.7-61.0)

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

044

1

5

8

2

1

8

2

5

8

1

5

8

2

1

8

2

5

8

1

5

8

2

5

8

3

1

8

054

1

5

8

2

5

8

3

1

8

1

5

8

2

5

8

3

1

8

064

Modules 124A,

124B,134A

1

5

8

2

1

8

2

5

8

1

5

8

2

1

8

2

5

8

1

5

8

2

5

8

3

1

8

1

5

8

2

5

8

3

1

8

1

5

8

2

5

8

3

1

8

074;

Module 134B

1

5

8

2

1

8

2

5

8

1

5

8

2

5

8

3

1

8

1

5

8

2

5

8

3

1

8

1

5

8

2

5

8

3

1

8

2

1

8

3

1

8

3

5

8

084

1

5

8

2

1

8

2

5

8

1

5

8

2

5

8

3

1

8

1

5

8

2

5

8

3

1

8

2

1

8

3

1

8

3

5

8

2

1

8

3

1

8

3

5

8

LEGEND

Not Required

Pipe A — Suction Riser Without Trap
Pipe B — Suction Riser With Trap
Pipe C — Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to de-

termine need for double suction risers.

2. Pipe sizes are based on the total linear length, shown for each

column, plus a 50% allowance for fittings.

3. Suction and liquid line sizing is based on pressure drop equivalent

to 2 F (1.1 C) at nominal rating conditions. Higher design pressure
drop criteria may allow selection of smaller pipe sizes but at a pen-
alty of decreased system capacity and efficiency.

4. Refer to Carrier System Design Manual or to E20-II design

programs for further information on selecting pipe sizes for split
systems.

5. All pipe sizes are OD inches. See Table 8A notes for metric

equivalents.

6. Refer to Fig. 13 for double suction riser construction.

18