Adjus t menu – tekmar 546 Thermostat Installation User Manual
Page 7
7 of 44
© 2008
D 546 - 07/08
Item Field
Range
Access
Description
50 to 100°F
(10.0 to 38.0°C)
LTD
USER
INST
ADV
SET COOL
SECTION
C
Select the cooling room temperature for each event.
Note: At the Limited Access Level, you can only
adjust the temperature +/-3°F (1.5°C) from the last
setting.
Away is only available when Scenes are turned on.
Wake
Default = 78°F (25.5°C)
UnOccupied
Default = 85°F (29.5°C)
Occupied
Default = 78°F (21.0°C)
Sleep
Default = 85°F (29.5°C)
Away
Default = 85°F (29.5°C)
OFF, 40 to 122°F
(OFF, 4.5 to 50.0°C)
LTD
USER
INST
ADV
FLOOR MINIMUM
SECTION
A
Select the minimum floor temperature for each
event.
Note: This item is only available when Sensor 1, 2,
or 3 is set to Floor. At the Limited Access Level, you
can only adjust the temperature +/-3°F (1.5°C) from
the last setting.
Wake
Default = 70°F (21.0°C)
UnOccupied
Default = OFF
Occupied
Default = 70°F (21.0°C)
Sleep
Default = OFF
40 to 122°F
(4.5 to 50.0°C)
Default = 85°F
(29.5°C)
ADV
FLOOR MAXIMUM
SECTION
A
Maximum floor temperature.
Note: This item is only available when Sensor 1, 2,
or 3 is set to Floor.
OFF, ROOM,
FLOR (Floor),
REM (Remote)
Default = OFF
INST
ADV
SENSOR 1
SECTION A
Select the type of sensor connected to auxiliary
sensor input 1.
OFF, ROOM,
FLOR (Floor),
OUT (Outdoor)
Default = OFF
INST
ADV
SENSOR 2
SECTION A
Select the type of sensor connected to auxiliary
sensor input 2.
OFF, ROOM,
FLOR (Floor),
COIL, DUCT
Default = OFF
INST
ADV
SENSOR 3
SECTION A
Select the type of sensor connected to auxiliary
sensor input 3.
Adjust Menu (2 of 7)
ADJUS
T MENU