Error Message

Description

SENSOR 2 OPEN CIRCUIT
Due to an open circuit, the thermostat failed to read Sensor 2. The thermostat displays the

error and continues to operate unless:
No other Room sensors are available and the thermostat is not connected to a tN4 System

control. Then the thermostat stops operation.
No other Floor sensors are available and the Floor Maximum is not set to Off, then the H1

contact no longer operates.
Locate and repair the problem as described in the Data Brochure D 070. Once the error is
corrected, the error message automatically clears.
SENSOR 3 SHORT CIRCUIT
Due to a short circuit, the thermostat failed to read Sensor 3. The thermostat displays the

error and continues to operate unless:
No other Room sensors are available and the thermostat is not connected to a tN4 System

control. Then the thermostat stops operation.
No other Floor sensors are available and the Floor Maximum is not set to Off, then the H1

contact no longer operates.
Sensor 3 is set to Duct. Then the ventilation feature is disabled.
Locate and repair the problem as described in the Data Brochure D 070. Once the error is
corrected, the error message automatically clears.
SENSOR 3 OPEN CIRCUIT
Due to an open circuit, the thermostat failed to read Sensor 3. The thermostat displays the

error and continues to operate unless:
No other Room sensors are available and the thermostat is not connected to a tN4 System

control. Then the thermostat stops operation.
No other Floor sensors are available and the Floor Maximum is not set to Off, then the H1

contact no longer operates.
Sensor 3 is set to Duct. Then the ventilation feature is disabled.
Locate and repair the problem as described in the Data Brochure D 070. Once the error is
corrected, the error message automatically clears.

SENSOR ERROR
All of the sensors have been set to Off or None including the built-in sensor and the tN4
System Control DIP switch is set to None. The thermostat stops operation.
Turn on at least one sensor or connect the thermostat to a tN4 system control and set the
tN4 System Control DIP switch to tN4 System Control.

COOL GROUP MASTER ERROR
Two thermostats have been set to the same COOL MST setting. Select a different COOL
MST setting for the thermostat. The cooling system will not operate while this error message
is present. The error message clears automatically once the error is corrected.

COOL GROUP MEMBER ERROR
The thermostat can no longer detect its cool group master. Check the communication
connections for open or short circuits. Once the cool group master has been detected, the
error message clears.

SCHEDULE MASTER ERROR
Two thermostats have been set to the same SCH MSTR setting. Select a different SCH MSTR
setting for the thermostat. The thermostat operates in the Occupied mode while this error
message is present. The error message clears automatically once the error is corrected.

Error Messages (3 of 4)