beautypg.com

Adjus t menu – tekmar 546 Thermostat Installation User Manual

Page 10

background image

© 2008

D 546 - 07/08

10 of 44

Item Field

Range

Access

Description

10 to 180 min

Default = 30

ADV

INTERLOCK

SECTION

G

Select how long heating must be off before cooling
starts.
Note: This item is only available when the Cool Stage
is set to 1 or 2.

HEAT, COOL

Default = COOL

ADV

PRIORITY HEATING OR COOLING

SECTION

G

Select whether heating has priority or cooling has
priority.
Note: This item is only available when the Cool Stage
is set to 1 or 2.

NONE, 1 to 5

Default = 1

INST

ADV

FAN MODE

SECTION

I

Select the operation of the Fan 1 and Fan 2 outputs.

OFF, ON

Default = OFF

INST

ADV

FAN 2 VENTILATION

SECTION

I

Select whether the Fan 2 output provides ventilation.
Note: This item is only available when the Fan Mode
is set to NONE, 1 or 2.

OFF, ON

Default = OFF

ADV

FAN 1 VENTILATION

SECTION

I

Select whether Fan 1 output is required to operate
while Fan 2 output provides ventilation.
Note: This item is only available when the Fan Mode
is set to None, 1 or 2 and F2 Vent is set to On.

OFF, 1 to 60 min

Default = OFF

ADV

VENTILATION PRE-VENT

SECTION

I

Select how long the ventilation operates continuously
prior to the Wake or Occupied events.
Note: This item is only available when the Fan Mode
is set to None, 1 or 2 and F2 Vent is set to On.

AUTO, OFF,

10% to 90%, ON

Default = AUTO

LTD

USER

INST

ADV

FAN OPERATION

SECTION

I

The minimum percentage of time the ventilation fan
operates during each event.
Auto operates with heat or cool.
On operates continuously.
% sets a minimum On time for each cycle.

Wake

UnOccupied

Occupied

Sleep

Adjust Menu (5 of 7)

Continued on next page.

ADJUS

T MENU