Adjus t menu – tekmar 546 Thermostat Installation User Manual
Page 10
© 2008
D 546 - 07/08
10 of 44
Item Field
Range
Access
Description
10 to 180 min
Default = 30
ADV
INTERLOCK
SECTION
G
Select how long heating must be off before cooling
starts.
Note: This item is only available when the Cool Stage
is set to 1 or 2.
HEAT, COOL
Default = COOL
ADV
PRIORITY HEATING OR COOLING
SECTION
G
Select whether heating has priority or cooling has
priority.
Note: This item is only available when the Cool Stage
is set to 1 or 2.
NONE, 1 to 5
Default = 1
INST
ADV
FAN MODE
SECTION
I
Select the operation of the Fan 1 and Fan 2 outputs.
OFF, ON
Default = OFF
INST
ADV
FAN 2 VENTILATION
SECTION
I
Select whether the Fan 2 output provides ventilation.
Note: This item is only available when the Fan Mode
is set to NONE, 1 or 2.
OFF, ON
Default = OFF
ADV
FAN 1 VENTILATION
SECTION
I
Select whether Fan 1 output is required to operate
while Fan 2 output provides ventilation.
Note: This item is only available when the Fan Mode
is set to None, 1 or 2 and F2 Vent is set to On.
OFF, 1 to 60 min
Default = OFF
ADV
VENTILATION PRE-VENT
SECTION
I
Select how long the ventilation operates continuously
prior to the Wake or Occupied events.
Note: This item is only available when the Fan Mode
is set to None, 1 or 2 and F2 Vent is set to On.
AUTO, OFF,
10% to 90%, ON
Default = AUTO
LTD
USER
INST
ADV
FAN OPERATION
SECTION
I
The minimum percentage of time the ventilation fan
operates during each event.
Auto operates with heat or cool.
On operates continuously.
% sets a minimum On time for each cycle.
Wake
UnOccupied
Occupied
Sleep
Adjust Menu (5 of 7)
Continued on next page.
ADJUS
T MENU