Room and Floor Sensor
When operating with both room and floor sensors, the
thermostat calculates an on time for the Heat 1 relay to
satisfy the floor sensor’s requirements and on times for
the Heat 1 and Heat 2 relays to satisfy the room sensor’s
requirements. The thermostat operates the Heat 1 relay
for the longer of these two on times.

While the minimum floor temperature is satisfied, the on
times of the Heat 1 and Heat 2 relays are calculated to
satisfy the room temperature requirements.

During heavy loads, the maximum floor temperature setting
limits the on time of the Heat 1 relay. In this situation, the
Heat 2 relay may be on while the Heat 1 relay is off.

Note: During light heating loads, overheating can occur
due to the minimum floor temperature requirements.

Zone Group

Heat 1 Pump = OFF
Zone Manager: Zone Group DIP = On

Operated by
Zone Manager

Operated by
tN4 System Control

Heat 1 Pump = On
Zone Manager: Zone Group DIP = OFF

Zone Group

1st

Stage

2nd

Stage

Mix Water Temperature Bus

Boiler Water Temperature Bus

System Pump Operation

When a tN4 System Control is used, each tN4 bus has a
system pump.

• If the tN4 bus’s system pump must turn on when the

Heat 1 relay is on, set the H1 Pump setting in the Adjust
menu to On.

• If the tN4 bus’s system pump must turn on when the

Heat 2 relay is on, set the H2 Pump setting in the Adjust
menu to On.

Second Stage Heat Source

The tN4 System Control needs to know whether second
stage heating operates a non-hydronic heating system, a
boiler water temperature zone, or a mixed water temperature
zone.

• If using non-hydronic, set to None.

• If using boiler temperature water, set to Boil.

• If using a mix water temperature, enter the correct Mix

bus number.

Thermal Motor Zone Valves

When using a thermal motor zone valve, system pump
operation must be delayed to allow the thermal motor zone
valve to fully open.

• When thermal motor zone valves are used set the Heat

1 Delay setting to On.