Misc menu – tekmar 546 Thermostat Installation User Manual

Page 22

background image

© 2008

D 546 - 07/08

22 of 44

Item Field

Range

Access

Description

LTD, USER,

INST, ADV

Default = USER

SEC

LTD

USER

INST

ADV

ACCESS LEVEL
The access level of the thermostat. The access column
shows which items are visible in each access level.
Note: This item is only available when the Lock /
Unlock DIP switch on the thermostat and the tN4
system control are set to Unlock.

°F, °C

Default = °F

USER

INST

ADV

UNITS

SECTION

T

Select Fahrenheit or Celsius as the temperature
units.

ON, TMPY, OFF

Default = TMPY

USER

INST

ADV

BACKLIGHT

SECTION

U

Select whether the backlight displays permanently,
temporarily, or is off. The temporary backlight lasts
for 30 seconds.

-5.0 to +5.0°F in

0.1°F increments

(-3.0° to +3.0°C in

0.1°C increments)

Default = 0.0°F

ADV

OFFSET

SECTION

Q

Fine tune the current room temperature. Adjustments
are in tenths of a degree.

– – –, -bus#:01,

... bus#:24, DEF

Default = – – –

INST

ADV

COPY SETTINGS

SECTION

V

Copy settings from another thermostat to this
thermostat.
1. Select the address of the thermostat to copy from.

Select DEF to load the factory default settings.

2. Wait for 3 seconds and then press the Up and Down

buttons for 1 second.

3. The thermostat will show the percentage of progress.
4. Displays DONE if successful or WARN if only part

of the settings were copied.

1 to 24

ADV

NUMBER OF DEVICES SECTION

U

Number of tN4 devices connected to this tN4 bus.
Note: This item is only available when the thermostat
is connected to a tN4 bus.

Misc (Miscellaneous) Menu (1 of 2)

The Miscellaneous menu items set display and control
options such as access level and temperature units.

Continued on next page.

MISC MENU