beautypg.com

tekmar 406 House Control Installation User Manual

Page 6

background image

©

2012 406_D

-

11/12

6

of

48

External Power Supply
It is strongly recommended that a transformer with an in-line
fuse be used in order to protect the transformer from high
currents. The tekmar Transformer 009 includes a fuse.

Connect the 24 V (ac) leads from the transformer to the C
and R terminals marked “Input Power” on the 406.

tekmarNet

®

2 Thermostats (tN2)

The 406 is designed to operate with tekmarNet

®

2 Thermostats.

They provide the heating and cooling control for each zone,
and communicate with any other tekmarNet

®

device on the

system.

Connect the tN2 terminals from each thermostat to the cor-
responding tN2 terminals for each zone on the 406.

Zone Valves

Wire the zone valves to the C and Vlv terminals on the 406.
End switches on zone valves are not required when using
the 406.

tN4 Expansion Terminals
The 406 uses the Expansion tN4 and C terminals to com-
municate with additional thermostats, setpoint controls, and
other tekmarNet

®

devices. Connect to either the Tank or the

Boil / Mix tN4 and C terminals on the 406.


Tank
To add additional Tank water temperature zones to the system,
install a tekmarNet

®

Wiring Center.

Connect the Tank terminals, tN4 and C, on the 406 to the
corresponding tN4 and C Expansion terminals on the ex-
ternal Wiring Center.

Boil / Mix
To add additional Boil or Mix water temperature zones to the
system, install a tekmarNet

®

Wiring Center.

Connect the Boil/Mix terminals, tN4 and C, on the 406 to
the corresponding tN4 and C Expansion terminals on the
external Wiring Center.

Domestic Hot Water (DHW) or Setpoint Call
When the control receives a DHW Call or Setpoint Call for heat
it will override Outdoor Reset and Indoor Feedback and operate
the boiler to heat the DHW tank or the Setpoint equipment.

To create a DHW call, wire a dry contact switch to the DHW
call terminals.
To create a Setpoint call, wire a dry contact switch to the
Setpoint call terminals.

Low Voltage Wiring -------------------------------------------------------------------------------------

-------------------------------------------------------------------------------------

Front Low Voltage Wiring Diagram ---------------------------------------------------------------------

---------------------------------------------------------------------

R

C

L

N

Expansion

tN4 Boil/Mix

Ct

N

4

Modulating

Boiler

—+

Expansion

tN4 Tank

Ct

N

4

tN2 tN2

tN2 tN2

tN2 tN2

tN2 tN2

1

Menu

House Control 406

Item

+

Ta

nk

Com

Boil

HP
Rt

Out

Com

Zone 1

H8009B

Zone 2

Zone 3

Zone 4

tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O/B

Sensors - No P

ow

er

No Power

Call

Call

Mix/DHW

tN4

tN4

CC

Mod dc/mA

Boil / Mix

Tank

Rc2

Y2

Se

tpoint

DHW

R

C

Input Power

Backup

Vlv

C

Vlv

C

Vlv

C

Zone 3

Zone 1

Zone 2

Zone 4

Vlv

C

24 V (ac) Transformer 009

DHW Call

from DHW

Tank Aquastat

(optional)

Setpoint Call

Outdoor Sensor

Mix Supply / DHW

Universal Sensor

Tank Supply

Universal Sensor

Boiler Supply

Universal Sensor

One Stage

Boiler T-T

tekmarNet

®

2 Thermostats

tekmarNet

®

4 Expansion to

Wiring Centers, Timers, or

User Switch

HP Return

Universal Sensor

One or Two Stage

Heat Pump

24 V (ac) Zone Valves