Mechanical

A406-1

Applications

Description: The House Control 406 operates a two stage air source heat pump in heating or cooling mode to supply an
outdoor reset water temperature to 4 on board tank temperature zones. Additional zones can be added using the Tank tN4 and
C Expansion terminals. Domestic Hot Water pre-heat is achieved by maintaining the DHW sensor S5 in the preheat storage
tank at an adjustable temperature, 90°F (32°C) default, using the DHW pump P6. The heat pump will target a water temperature
20°F (11°C) higher than the preheat tank target at the return sensor S2, and is limited by the

HP RETURN MAX

setting in the

Adjust Menu. An electric element in the system storage tank is switched on through an isolation relay with the backup relay on
the 406 to provide backup heat to maintain the Tank Sensor S4 at its target temperature.
Tank zones can have fan-coils, air handling units, chilled beams, or chilled panels as their terminal units depending on the type
of tekmarNet

®

thermostat selected.

Expansion

Tank

Electric

Element

Backup

Freeze

Protection

Device

Electric

Water

Heater

S1

S4

S2

tekmarNet

®

2 Thermostats

P4

P2

Z1

Z2

Z3

Z4

Coaxial

Heat Exchanger

Cold In

Two Stage

Air to Water

Heat Pump

Preheat

Storage Tank

P6

S5

DHW Out

WATER TEMP

T (tank)

BACKUP

AUX (auxiliary)

HP LOOP

INT (intermittent)

HP TYPE

2STG (2-stage)

DHW MODE

5 (DHW preheat)

Application Settings

P2

HP Loop Pump

P4

Tank System Pump

P6

DHW Pump

S1

Outdoor Sensor

S2

HP Return Sensor

S4

Tank Sensor

S5

DHW Sensor

Legend

406