Adjust Menu (4 of 6)

Item Field

Range

Description

35 to 70°F

(4 to 21°C)

Default = 50°F

(10°C)

Access: Installer
Set to:

COOL SETPOINT

SECTION D

Tank setpoint that will be maintained when in cooling mode (not for floor
cooling).

ON, OFF

Default = ON

Access: Installer
Set to:

DEW POINT

SECTION C

ON - a humidity sensor is required in order to operate floor cooling.
OFF - no humidity sensor is required to perform floor cooling. The floor-cooling
supply target will be the value of the COOL MINIMUM setting.

OFF, 40 to 75°F

(4.5 to 24°C)

Default = 60°F

(15.5°C)

Access: Installer
Set to:

COOL MINIMUM

SECTION C

Minimum supply temperature to deliver when:

Performing floor cooling for a loop
Limiting a zone’s target supply temperature based on dewpoint
considerations.

The target for floor-cooling or dewpoint limiting is calculated as the higher of:

2 °F above the dewpoint or this setting.


O, B

Default = O

Access: Installer
Set to:

SWITCHOVER

SECTION E

O - Close O/B contacts to operate heat pump in cool mode.
B - Close O/B contacts to operate heat pump in heat mode.

2 to 20°F

(1 to 11°C)

Default = 4°F

Access: Installer
Set to:

HEAT PUMP DIFFERENTIAL

SECTION E

Differential around the tank sensor which the heat pump will cycle its compressor
(half above and half below target).

AUTO, 2:00 to
20:00 minutes

Default = AUTO

Access: Installer
Set to:

HEAT PUMP 2 DELAY

SECTION E

The minimum time delay between the Y1 and Y2 stages of the heat pump.
Note: Item is only available when HP TYPE = 2STG or ROT.

INTR, ON

Default = INTR

Access: Installer
Set to:

HP LOOP

SECTION B

INTR - The HP Loop Pump will operate together with the heat pump including
pre & post purge
ON - The HP Loop Pump will operate whenever heat is being drawn from or
pushed into the tank:

When heat pump operates including pre & post purge
When there is a tank call
When there is a mix call
When the transfer pump is running




70 to 180°F

(21 to 82°C)

Default = 100°F

(38°C)

Access: Installer
Set to:

HP RETURN MAXIMUM

SECTION E

Prevents the heat pump from operating in heating mode if the heat pump return
temperature exceeds this setting.