Adjust Menu (4 of 4)

D1

Setpoint Mode Selects the Setpoint mode of
operation.

1 (parallel, no priority),

2 (parallel, priority),
3 (primary pump)
Default = 1

D1

Setpoint Occupied The minimum target supply
temperature when a setpoint demand is present during
the Occupied period. This item is only available when the

Boiler Sensor Return / Supply DIP switch is set to Supply.

OFF, 60 to 220°F
(OFF, 16 to 104°C)
Default = 180°F (82°C)

D1

Setpoint Unoccupied Selects whether or not a setpoint
demand will be responded to during the Unoccupied
period. This item is only available when the

Boiler

Sensor Return / Supply DIP switch is set to Supply and

when the

Setback / Off DIP switch is set to Setback.

OFF, On
Default = OFF

A

WWSD Occupied The system’s warm weather shut
down temperature during the Occupied period. This
item is only available when Mix 1 Mode is set to 1
and / or Mix 2 Mode is set to 1 and / or the

Boiler Sensor

Return / Supply DIP switch is set to Supply.

35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 70°F (21°C)

A

WWSD Unoccupied The system’s warm weather shut
down temperature during the Unoccupied period.
This item is only available when Mix 1 Mode is set to
1 or Mix 2 Mode is set to 1 and / or the

Boiler Sensor

Return / Supply DIP switch is set to Supply and the

Setback / Off DIP switch is set to Setback.

35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 60°F (21°C)

The units of measure that all of the temperatures are to
be displayed in by the control.

°F,°C
Default = °F

Display

Description

Range

Section

Installer