Adjust menu (3 of 4), Display description range, Actual setting – tekmar 374 Universal Reset Control User Manual
Page 28

© 2009 D 374 - 03/09
28 of 36
Adjust Menu (3 of 4)
A
Boiler Terminal Unit The type of terminal units that are 
being used in boiler zones. This item is only available 
when the 
Boiler Sensor Return / Supply DIP switch is set
to
Supply.
1 (HRF1), 2 (HRF2), 
3 (COIL), 4 (CONV), 
5 (RAD), 6 (BASE)
Default = 4
B1
Boiler Indoor The design indoor air temperature used 
in the heat loss calculation for the boiler zones. This item 
is only available when the 
Boiler Sensor Return / Supply
DIP switch is set to
Supply.
35 to 100°F
(2 to 38°C)
Default = 70°F (21°C)
B1
Boiler Design The design supply water temperature 
used in the heat loss calculations for the heating system. 
This item is only available when the 
Boiler Sensor
Return / Supply DIP switch is set to Supply.
70 to 220°F
(21 to 104°C)
B1
Boiler Minimum The minimum allowed boiler target 
temperature and boiler protection temperature. Check the 
boiler(s) manufacturer’s manual for recommend supply 
water temperatures. 
OFF, 80 to 180°F
(OFF, 27 to 82°C)
B1
Boiler Maximum The maximum allowed boiler target 
temperature. This item is only available when the 
Boiler
Sensor Return / Supply DIP switch is set to Supply.
120 to 225°F
(49 to 107°C)
B1
Fire Delay The time delay the control can expect between 
the time that the relay contact closes to fire the boiler and 
when the burner actually fires. This item is only available 
when the 
Boiler Sensor Return / Supply DIP switch is set
to
Supply.
0:00 to 3:00 minutes
(1 sec increment)
Default = 0:10 min
B1
Boiler Mass The thermal mass characteristics of the 
boilers that are being used. This item is only available 
when the 
Boiler Sensor Return / Supply DIP switch is set
to
Supply.
1 (Lo), 2 (Med), 3 (Hi)
Default = 2
B1
Stage Delay The minimum time delay between the 
operation of stages. This item is only available when 
the 
Boiler Sensor Return / Supply DIP switch is set to
Supply.
Au, 0:30 to 20:00 
minutes
(5 sec increments)
Default = Au
B1
Boiler Differential The temperature differential that the 
control is to use when it is operating the boiler(s). This item 
is only available when the 
Boiler Sensor Return / Supply
DIP switch is set to
Supply.
Au, 2 to 42°F
(Au, 1 to 23°C)
Default = Au
C1
DHW Mode Selects the DHW mode of operation.
1 (parallel, no priority),
2 (parallel, priority),
3 (pri-sec, no priority),
4 (pri-sec, priority)
Default = 1
C1
DHW Exchange Occupied The minimum boiler 
temperature to the DHW heat exchanger during the 
Occupied period. This item is only available when the 
Boiler Sensor Return / Supply DIP switch is set to Supply.
OFF, 100 to 220°F
(OFF, 38 to 104°C)
Default = 180°F (82°C)
C1
DHW Exchange Unoccupied Selects whether the 
control should respond to DHW demands during the 
Unoccupied period. This item is only available when the 
Boiler Sensor Return / Supply DIP switch is set to Supply
and the
Setback / Off DIP switch is set to Setback.
OFF, On
Default = OFF
Display
Description
Range
Section
Installer
Ad
v
Actual
Setting