BOILER START (Boil STRT)

(

RESET

RATIO

)

The Boil STRT

temperature is the boiler supply water temperature that the

heating system requires when the outdoor air temperature equals the
OUT STRT

air temperature setting.

OUTDOOR START (OUT STRT)

(

RESET

RATIO

)

The OUT STRT

temperature is the outdoor air temperature at which the

control provides the Boil STRT supply water temperature

to the system.

OUTDOOR DESIGN (OUT DSGN)
(

RESET

RATIO

&

CHARACTERIZED

HEATING

CURVE

)

The OUT DSGN is the outdoor air temperature that is the typical coldest
temperature of the year where the building is located. This temperature is
used when doing heat loss calculations for the building.

BOILER DESIGN (Boil DSGN)
(

RESET

RATIO

&

CHARACTERIZED

HEATING

CURVE

)

The Boil DSGN temperature is the supply water temperature required to
heat the boiler zones when the outdoor air is as cold as the OUT DSGN
temperature.

BOILER MINIMUM (Boil MIN)
(

RESET

RATIO

&

CHARACTERIZED

HEATING

CURVE

)

The Boil MIN is the lowest water temperature that the control is allowed to
use as a Boil TRG

temperature. During mild conditions, if the 262 calculates

a Boil TRG

temperature that is below the Boil MIN setting, the Boil TRG

temperature is adjusted to at least the Boil MIN setting. During this
condition, if the boiler is operating, the

Minimum pointer turns on in the LCD

while the Boil TRG

or the Boil SUP temperature is viewed. If the installed

boiler(s) is designed for condensing operation, set the Boil MIN adjustment
to OFF.

BOILER MAXIMUM (Boil MAX)
(

RESET

RATIO

&

CHARACTERIZED

HEATING

CURVE

)

The Boil MAX is the highest water temperature that the control is allowed to
use as a Boil TRG temperature. If the control does target Boil MAX, and the
Boil SUP temperature is near the Boil MAX temperature, the

Maximum

pointer turns on in the LCD while the Boil TRG or the Boil SUP temperature is
viewed. At no time does the control operate the boiler(s) above 248˚F (120˚C).

WARM WEATHER SHUT DOWN (WWSD) OCC & UNOCC
(

RESET

RATIO

&

CHARACTERIZED

HEATING

CURVE

)

When the outdoor air temperature rises above the WWSD setting, the 262
turns on the

WWSD pointer in the display. When the control is in Warm

Weather Shut Down, the

Boiler Demand pointer is displayed if there is a

demand. However, the control does not operate the heating system to
satisfy this demand. The control does respond to either a

DHW Demand

or a

Setpoint Demand and operates as described in Section C.

BOILER SETBACK (SETBACK)

(

RESET

RATIO

)

The boiler SETBACK is the amount that the boiler supply water temperature
is reduced when the 262 is placed into an

UnOccupied mode, using an

internal or an external setback as described in Section A. This setting is
only available if the

Reset Ratio DIP switch is selected and Setback / None

DIP switch is set to

Setback.

BOILER INDOOR (Boil INDR)
(

CHARACTERIZED

HEATING

CURVE

)

The Boil INDR is the room temperature used in the heat loss calculations
done for the building. This setting establishes the beginning of the

Charac-

terized Heating Curve for the boiler zones. This single setting replaces the
Boil STRT water temperature and OUT STRT air temperature settings used
by the

Reset Ratio.

Sequence, Section B1

Boil Max + 1/2 Boiler Differential

Boil Max - 1/2 Boiler Differential

Boil W

ate

r Te

mp

era

tur

e

Pointer On

Pointer On

Boil MAX

Pointer On

Boil MIN

Boil Wat

er Te

mpe

ratu

re

Boil Min + 1/2 Boiler Differential

Boil Min - 1/2 Boiler Differential

70

(21)

90

(32)

110

(43)

130

(54)

150

(66)

170

(77)

190

(88)

Outdoor Air Temperature

Supply W

ater

T

emperature

210

(99)

-20

(-29)

0

(-18)

20

(-7)

40

(5)

60

(16)

80

(27)

Boil DSGN

Boil MAX

Boil MIN

OUT STRT

WWSD Unocc

Boil SETB

OUT DSGN

Boiler Reset

Ratio

WWSD Occ

Boil STRT

70

(21)

90

(32)

110

(43)

130

(54)

150

(66)

170

(77)

190

(88)

Outdoor Air Temperature

Supply W

ater

T

emperature

210

(99)

-20

(-29)

0

(-18)

20

(-7)

40

(5)

60

(16)

80

(27)

Boil DSGN

Boil MAX

Boil MIN

WWSD Unocc

Boil IND

OUT DSGN

Boiler Characterized

Heating Curve

WWSD Occ

50

(10)

Boil ROOM Occ

Boil ROOM UnOcc