tekmar 262 Boiler Control Installation User Manual

Page 22

background image

22 of 36

Copyright © D 262 -

12/08

Section

262 Adjust Menu (2 of 4)

The design supply water temperature used in the
heat loss calculations for the heating system.

MODE = —1—

70 to 220˚F
(21 to 104˚C)

Default = 190

°F (88°C)

The design outdoor air temperature used in the
heat loss calculations for the heating system.

MODE = —1—

-60 to 32˚F
(-51 to 0˚C)

Default = 10

°F (-12°C)

The maximum boiler target supply water
temperature.

120 to 225˚F, OFF
(49 to 107˚C, OFF)

Default = 210

°F (99°C)

The starting water temperature used in the reset
ratio calculation for the heating system.

DIP switch =

Reset Ratio

MODE = —1—

The minimum temperature allowed for the boiler
target temperature.

35 to 150˚F
(2 to 66˚C)

Default = 70

°F (21°C)

OFF, 80 to 180˚F
(OFF, 27 to 82˚C)

Default = 140

°F (60°C)

35 to 85˚F
(2 to 29˚C)

Default = 70

°F (21°C)

The outdoor starting temperature used in the
reset ratio calculation for the heating system.

DIP switch =

Reset Ratio

MODE = —1—

The time delay the control can expect between
the time the boiler contact closes and the burner
fires.

0:00 to 3:00 min
(in 1 sec. increments)

Default = 0:10 min

The thermal mass characteristics of the boilers
that are being used.

LITE, MED, HEVY

Default = MED

The differential that the control is to use when it
is operating the boiler(s).

AUTO, 2 to 42˚F
(AUTO, 1 to 23˚C)

Default = AUTO

Selects stage 1 as operational or not.

AUTO, OFF

Default = AUTO

Selects stage 2 as operational or not.

Sets the rotation time for the stages. This item is
used by the

Equal Run Time Rotation function.

10 to 72 hr, OFF

Default = 48 hr

The device that is being used to supply flow to
the heat exchanger in the DHW storage tank.

No Indirect DHW tank = NONE
MODE = —1—

NONE, PUMP, VALV

Default = PUMP

AUTO, OFF

Default = AUTO

Selects if a tekmar sensor is being used to
m e a s u r e t h e D H W t a n k t e m p e r a t u r e .

DHW THRU

≠ NONE

NONE, DHW

Default = NONE

Actual

Setting

LT

D

USER INST ADV

Range

Access
Level

Description

Item Field

B1

B1

B1

B1

B1

B1

A

A

A

A

A

A

C1