beautypg.com

Boiler demand, Dhw demand, Setpoint demand – tekmar 262 Boiler Control Installation User Manual

Page 15: Output connections boiler pump contact (boil p1), Dhw pump / valve contact, Boiler contacts, Sensor and unpowered input connections, Outdoor sensor, Boiler sensor

background image

15 of 36

Copyright © D 262 -

12/08

Boiler Demand

To generate a Boiler Demand, a voltage between 24 V (ac) and 240 V (ac) must be
applied across the

Boiler Demand terminals (1 and 2).

DHW Demand

To generate a DHW Demand, a voltage between 24 V (ac) and 240 V (ac) must be applied
across the

Com Dem and the DHW Dem terminals (3 and 4).

Setpoint Demand

To generate a Setpoint Demand, a voltage between 24 V (ac) and 240 V (ac) must be
applied across the

Com Dem and the Setp Dem terminals (3 and 5).

Caution: The same power supply must be used for both the DHW demand and setpoint
demand circuits since they share the

Com Dem terminals.

Output Connections

Boiler Pump Contact (Boil P1)

The boiler pump output terminal (8) on the 262 is a powered output. When the relay
contact in the 262 closes, 120 V (ac) line (L) is provided to the

Boil P1 terminal (8) from

the

Power L terminal (7). To operate the boiler pump, connect one side of the boiler pump

circuit to terminal 8 and the second side of the pump circuit to the neutral (N) side of the
120 V (ac) power supply.

DHW Pump / Valve Contact

The

DHW Pump / Valve terminals (9 and 10) are an isolated output in the 262. There is

no power available on these terminals from the control. These terminals are to be used
as a switch to either make or break power to the DHW pump or the DHW valve. Since
this is an isolated contact, it may switch a voltage between 24 V (ac) and 240 V (ac).

Boiler Contacts

The

Stage 1 and Stage 2 terminals (11, 12 and 13, 14) are isolated outputs in the 262.

There is no power available on these terminals from the control. These terminals are to
be used as a switch to either make or break the boiler circuit. When the 262 requires the
boiler(s) to fire, it closes the contact between terminals 11 and 12 and/or 13 and 14.

Sensor and Unpowered Input Connections

Do not apply power to these terminals as this damages the control.

Outdoor Sensor

Connect the two wires from the Outdoor Sensor 070 to the

Com and

Out terminals (19 and 22). The Outdoor Sensor is used by the 262 to
measure the outdoor air temperature.

Boiler Sensor

Connect the two wires from the Boiler Sensor 071 to the

Com and Boil

terminals (19 and 21). The Boiler Sensor is used by the 262 to
measure the supply (outlet) water temperature from the boiler(s).

1

2

24 to 240 V (ac)

Boiler

Demand

3

4

Com

Dem

DHW

Dem

24 to 240 V (ac)

3

4

Com

Dem

DHW

Dem

Setp

Dem

5

24 to 240 V (ac)

N

L

Boil
P1

8

7

6

Power

120 V (ac)

L

N

9

10

DHW

Pmp/Vlv

24 to 240 V (ac)

M

or

11 12

Stage

13 14

1

1

Stage

2

2

T

T

T

T

T

T

T

T

19

20

Com

DHW Boil

21

22

Out

19

20

Com

DHW

Boil

21

22

Out

Boiler
sensor