262 Adjust Menu (3 of 4)

The DHW storage tank’s temperature during the
Occupied period.

DHW SENS = DHW
DHW THRU

≠ NONE

The DHW storage tank’s temperature during the
UnOccupied period.

DIP switch =

Setback

DHW SENS = DHW
DHW THRU

≠ NONE

OFF, 70 to 190˚F
(OFF, 21 to 88˚C)

Default = 140

°F (60°C)

OFF, 70 to 190˚F
(OFF, 21 to 88˚C)

Default = 120

°F (49°C)

Occ

UnOcc

Sets the differential for the DHW storage tank.

DHW SENS = DHW
MODE = —2—

1 to 42˚F
(1 to 23˚C)

Default = 6

°F (3°C)

Actual

Setting

LT

D

USER INST ADV

Range

Access
Level

Description

Item Field

C1

C1

C4

The minimum boiler supply temperature to the
DHW heat exchanger during the Occupied period.

DHW SENS = NONE
DHW THRU

≠ NONE

Selects whether or not DHW will be generated
during the UnOccupied period.

DIP switch =

Setback

DHW SENS = NONE
DHW THRU

≠ NONE

OFF, 100 to 220˚F
(OFF, 38 to 104˚C)

Default = 180

°F (82°C)

OFF,
DHW XCHG
Occ setting

Default = OFF

UnOcc

Occ

Enables or disables the DHW priority function
over the heating load.

DHW THRU = PUMP
MODE = —1—

The minimum boiler supply temperature when a
setpoint demand is present during the Occupied
period.

MODE = —1—

NONE, BOIL

Default = BOIL

OFF, 70 to 220˚F
(OFF, 21 to 104˚C)

Default = 180

°F (82°C)

Occ

UnOcc

Selects whether or not a setpoint demand will be
responded to during the UnOccupied period.

DIP switch =

Setback

MODE = —1—

OFF,
SETPOINT
Occ setting

Default = OFF

Selects whether or not the setpoint demand will
have priority over the heating system.

MODE = —1—

NONE, BOIL

Default = NONE

The system’s warm weather shut down during the
Occupied period.

MODE = —1—

35 to 100˚F, OFF
(2 to 38˚C, OFF)

Default = 70

°F (21°C)

Occ

C1

C1

C2

D1

D1

D1

B1