beautypg.com

Testing the wiring, Pg 16, Dhw sensor – tekmar 262 Boiler Control Installation User Manual

Page 16: 10k sensor, Zone control input, Tekmar net, Device (tn1 / tn2), Unoccupied switch, Step five testing the wiring, Test the sensors

background image

16 of 36

Copyright © D 262 -

12/08

DHW Sensor

Connect the two wires from the DHW Sensor 071 to the

Com and DHW

terminals (19 and 20). The DHW Sensor is used by the 262 to measure
the DHW tank temperature.

10K Sensor

Either an Indoor Sensor, Slab Sensor, or Zone Control may be
connected to the

10K input. If a sensor is used, connect the two wires

from the sensor to the

Com and 10K terminals (16 and 17).

Zone Control Input

If an external tekmar Zone Control is used, connect the wire from the
Com Sen terminal on the Zone Control to the Com terminal (16) on the
262. Connect the

Zo Out terminal on the Zone Control to the 10K

terminal (17) on the 262.

Note: The wires from the Zone Control are polarity sensitive. The
communication does not operate correctly if the wires are reversed.

tekmar Net

TM

Device (tN1 / tN2)

A Room Temperature Unit (RTU) 062 or 063, or a Remote Display
Module (RDM) 040 may be connected to the

tekmar Net

TM

tN1 / tN2

input. Connect the

Com terminal from the appropriate device to the

Com terminal (16) on the 262. Connect the tekmar Net

TM

tN1 or tN2

terminal from the appropriate device to the

tekmar Net

TM

tN1 / tN2

terminal (15) on the 262.

Note: The wires from the RTU and the RDM are polarity sensitive. The
tekmar Net

TM

tN1 / tN2 device does not operate correctly if the wires

are reversed.

UnOccupied Switch

If an external timer (tekmar Timer 03

2) or switch is used, connect the

two wires from the external switch to the

Com and UnO Sw terminals

(16 and 18). When these two terminals are shorted together, the
control registers an UnOccupied signal.

Note: The setback override in the schedule menu of the control
overrides any external signal that is present at the UnOccupied Switch
terminals.

STEP FIVE

TESTING THE WIRING

Each terminal block

must be unplugged from its header on the control before power is applied for testing. To remove the terminal block,

pull straight down from the control.

The following tests are to be performed using standard testing practices and procedures and should only be carried out by properly
trained and experienced persons.

A good quality electrical test meter, capable of reading from at least 0 - 300
V (ac) and at least 0 - 2,000,000 Ohms, is essential to properly test the
wiring and sensors.

Test the Sensors

In order to test the sensors, the actual temperature at each sensor
location must be measured. A good quality digital thermometer with a
surface temperature probe is recommended for ease of use and accuracy.
Where a digital thermometer is not available, a spare sensor can be
strapped alongside the one to be tested and the readings compared. Test
the sensors according to the instructions in the Data Brochure D 070.

19

20

Com DHW

16

17

Com 10K

15

16

tN1 /

tN2

Com

Item

Menu

UnOcc 1

°F

View

Heat

Com
Sen

Zo

Out

tekmar 262

Zone Control

16

17

10K

Com

16

17

Com

10K

UnO

Sw

18

Timer Switch

V

19

20

Com

DHW

Boil

21

22

Out