Page 5

CLOSE OFF DATA

Close Off Ratings for Normally Closed Valves

Close Off (

P in psi)

Signal-to-Actuator

Valve Size

Actuator

(Positioner)

(in)

(in

2

)

3-15 PSI

1-17 PSI

0-30 PSI

2.5

46

26

53

106

100 (1U)

96

125

125

3

46

15

34

70

100 (1U)

63

92

92

4

46

6

16

36

100 (1U)

32

48

48

5

100 (1U)

19

29

29

6

100 (1U)

12

19

19

50

250

200

150

100

50

300

150

100

Pressure — psig

Temperature —

¡

F

200

Maximum Media

Temperature

281¡F

Minimum Media

Temperature

40¡F

169 psig

596SI

Figure 3 - Temperature and Pressure Ratings

Close Off Ratings for Normally Open Valves

Close Off (

P in psi)

Signal-to-Actuator

Valve Size

Actuator

(Positioner)

(in)

(in

2

)

3-15 PSI

1-17 PSI

0-30 PSI

2.5

46

49

86

125

100 (1L)

125

125

125

3

46

32

58

125

100 (1L)

90

118

125

4

46

15

30

77

100 (1L)

48

64

125

5

100 (1L)

29

39

105

6

100 (1L)

19

26

72

TEMPERATURE/PRESSURE RATINGS

In all cases, do not exceed the temperature/pressure
ratings of the valve (see figure 3). Acceptable region is
shown by the shaded area.

In all cases requiring greater close off, a preload adjustment is possible. Consult with factory for your application.