beautypg.com

Powers PowerStation XP Single and Multi-Valve Series - Triple Valve 1 - 416 gpm User Manual

Page 4

background image

USA:  Phone: 1.800.669.5430 • Fax 1.847. 229.0526 • www.powerscontrols.com

Canada:  Phone: 1.888.208.8927 • Fax 1.888.479.2887 • www.powerscontrols.ca

IS-P-SF-TVPS 0931

EDP# 6512311

© 2009 Powers

What to look for if:
• Recirculation temperature rises when there is no demand on

the system:

1. Refer to Aquastat or Continuous Recirculation Instructions
• Outlet temperature is too hot with low flow (#1):
1. The thermal actuator of the valve is not working properly.

Test and replace accordingly to the appropriate installation

instructions, IS-P-SH1430 enclosed.

• Outlet temperature is too hot with a high flow (#2 or #3):
1. The thermal actuator of the valve is not working properly.

Test and replace accordingly, IS-P-MM430.

• Outlet temperature too low with low or high flow:
1. The hot water temperature is too low. You must have a sup-

ply temperature of at least 5°F (3°C) higher than the set tem-

perature. Readjust the hot water supply.

2. The checkstops on the hot side of the valve are not fully

open, or may be stuck due to liming. Open and clean check-

stops.

3. The temperature has not been set properly on the low and/or

high valve. Refer to set up procedure and reset the valves.

• Outlet flow drops off:
1. The checkstops are not fully open or stuck. Open and clean

checkstops.

2. The system pressure varies by more than 50% of the inlet

supply pressure.

• Outlet temperature cycles between hot and cold:
1. The system pressure varies by more than 50% of the inlet

supply pressure.

2. The valve system may be oversized for application. Check

system sizing to verify.

3. Recirculation may not be balanced properly. Refer to

Aquastat or Continuous Recirculation instructions.

Troubleshooting

n

Thermostatic water mixing valves are control devices which

must be cleaned and maintained on a regular basis.
1. Before servicing checkstops or piping, turn off the water

upstream. At least every twelve (12) months, open up the

checkstops and check for the free movement of the poppet.

2. Before servicing the valve, turn off the water supply upstream

or close the checkstops. To close the checkstops, turn the

adjusting screw clockwise.

3. When opening checkstops after servicing, do not over adjust;

turn adjusting screw fully counterclockwise and then 1/2 turn

clockwise.

4. Every three (3) months, check the maximum temperature

adjustments.

5. Every twelve (12) months, remove the valve bonnets and

check the internal components for freedom of movement.

CAUTION:
Any changes in supply condition could effect the out-

let water temperature. Check and adjust the valves

accordingly to prevent injury to the users.

Preventative Maintenance

n

See enclosed IS-P-MM430 and IS-P-SH1430.

Part List For Valve

n

Warranty

n

The Seller warrants that the equipment manufactured by it and covered by this order or contract is free from defects in material and workmanship and, without

charge, equipment found to be defective in material or workmanship will be repaired, or at Seller’s option replaced F.O.B. original point of shipment, if written

notice of failure is received by Seller within one (1) year after date of shipment (unless specifically noted elsewhere), provided said equipment has been properly

installed, operated in accordance with the Seller’s instructions, and provided such defects are not due to abuse or decomposition by chemical or galvanic action.

ThiS expreSS warranTy iS in lieu OF and excludeS all OTher warranTieS, guaranTeeS, Or repreSenTaTiOnS, expreSS OF implied. There are

nO implied warranTieS OF merchanTaBiliTy Or OF FiTneSS FOr a parTicular purpOSe. The Seller assumes no responsibility for repairs made on the

Seller’s equipment unless done by the Seller’s authorized personnel, or by written authority from the Seller. The Seller makes no guarantee with respect to material

not manufactured by it.

NOTE: AFTER COMPLETING REPAIRS,

CHECK DISCHARGE TEMPERATURE.

RESET IF NECESSARY.

WARNING: FAILURE TO PERFORM THIS

OPERATION COULD RESULT IN UNSAFE

DISCHARGE TEMPERATURE, WHICH MAY

CAUSE INJURY OR DEATH.

!

A Watts Water Technologies Company