Powers PowerStation XP Single and Multi-Valve Series - Triple Valve 1 - 416 gpm User Manual
Technical instructions

Description
n
Capacity
n
Triple Valve PowerStation
™
Capacity up to 416 gpm
Technical Instructions
IS-P-SF-TVPS
Advanced Thermal Activation
Maximum Operating Pressure ............................. 125psi (861 kPa)
Maximum Hot Water Temperature ...................... 200°F (93°C)
Minimum Hot Water Supply Temp.* ................... 5°F (3°C) above set point
Hot Water Inlet Temperature Range ................... 120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range ................. 40 - 80°F (4 - 27°C)
Minimum Flow** ...................................................... 0.5 gpm (1.89 lpm)
Temperature Adjustment Range *** ................... 90 - 160°F (32 - 71°C)
Listing/Compliance (Valves only) .......................... ASSE 1017, CSA B125
* With Equal Pressure
** Minimum flow when Hi/Lo is installed at or near hot water source recirculating tempered
water with a properly sized continuously operating recirculating pump.
*** Note: Low limit cannot be less than the cold water temperature. For best operation, hot
water should be at least 5°F (3°C) above desired set point.
Specifications
n
Flow Capacity at 50-50 Mixed Ratio
P r e s s u r e D r o p A c r o s s V a l v e
Model
Min. Flow
C
V
5psi
10psi
20psi
30psi
45psi
60psi
to ASSE 1017
(34 kPa)
(69 kPa)
(138 kPa)
(207 kPa)
(310 kPa)
(414 kPa)
SH1434TV and
LFSH1434TV
1 gpm
62.00
139 gpm
196 gpm
277 gpm
340 gpm
416 gpm
480 gpm
4 lpm
526 lpm
742 lpm
1049 lpm
1287 lpm
1575 lpm
1817 lpm
PowerStation
™
is a complete, fully assembled water tempering system,
designed to provide safe water throughout commercial and institutional
facilities. PowerStation
™
features the HydroGuard
®
XP MM430 or LFMM430
and SH1430 or LFSH1430 master tempering series valves which utilize
paraffin-based actuation technology to sense and adjust outlet temperature.
Each PowerStation
™
is mounted on heavy-duty, welded struts and factory
tested as a complete system. Each PowerStation
™
includes an engineer
specified circulator, GFCI outlet, combination temperature/pressure gauges
and Powers' triple-duty checkstops. Optional equipment includes an
Aquastat.
WARNING: TO ENSURE THE
ACCURATE AND RELIABLE
OPERATION OF THIS PRODUCT, IT IS
ESSENTIAL TO:
• Properly size each valve based on the indi-
vidual application.
• Properly design the recirculation system to
minimize pressure and temperature variations.
• Conduct an annual maintenance program to
ensure proper operation of all critical com-
ponents.
THIS VALVE MUST BE USED IN
CONJUNCTION WITH TEMPERATURE
ACTUATED POINT-OF-USE DEVICES THAT
COMPLY WITH ASSE 1016, 1069, OR 1070.
FAILURE TO COMPLY WITH PROPER
INSTALLATION INSTRUCTIONS COULD
CONTRIBUTE TO VALVE FAILURE, RESULTING
IN IN JURY OR DEATH.
!