Warranty, Troubleshooting instructions – Powers 460 Series AquaSentry 2 Temperature Alarm System User Manual
Page 4

USA: Phone: 1.800.669.5430 • Fax 1.847. 229.0526 • www.powerscontrols.com
Canada: Phone: 1.888.208.8927 • Fax 1
.
888
.
479
.
2887
•
www.powerscontrols.ca
IS-P-MV460AS 1327
EDP# 6509000
© 2013 Powers
Warranty
n
The Seller warrants that the equipment manufactured by it and covered by this order or contract is free from defects in material and workmanship and, without
charge, equipment found to be defective in material or workmanship will be repaired, or at Seller’s option replaced F.O.B. original point of shipment, if written
notice of failure is received by Seller within one (1) year after date of shipment (unless specifically noted elsewhere), provided said equipment has been properly
installed, operated in accordance with the Seller’s instructions, and provided such defects are not due to abuse or decomposition by chemical or galvanic action.
ThIS exPreSS wArrAnTy IS In lIeu OF And excludeS All OTher wArrAnTIeS, guArAnTeeS, Or rePreSenTATIOnS, exPreSS OF IMPlIed. There
Are nO IMPlIed wArrAnTIeS OF MerchAnTABIlITy Or OF FITneSS FOr A PArTIculAr PurPOSe. The Seller assumes no responsibility for repairs made
on the Seller’s equipment unless done by the Seller’s authorized personnel, or by written authority from the Seller. The Seller makes no guarantee with respect to
material not manufactured by it.
A Watts Water Technologies Company
WARNING: This product contains chemicals known to the
State of California to cause cancer and birth defects or
other reproductive harm.
For more information: www.watts.com/prop65
1. The Aqua Sentry 2
®
has been carefully engineered to be as
simple to install, and as reliable as possible. Should you have
difficulty, please use the following guide to identify the cause of
the problem.
Display does not light up
• Make sure the power is on.
• Ensure the transformer is properly wired to terminals 1 and 2 or
the control unit.
Display indicates 205° or has a negative reading all the
time
• Sensor is not plugged into the junction box.
• Junction box is incorrectly wired to the control unit; check wir-
ing, and correct.
• Sensor probe is defective.
Display flashes continuously and cannot be reset
• Check the alarm setpoints, ensure the actual temperature is
between the low and high setpoints.
Troubleshooting Instructions
n
Operate
Set
HSP
LSP
Set
Set
Enter high alarm trip point*
Enter low alarm trip point.*
Enter calibration offsets.
“105”
Set
Set
Set
“035”
CAL
Set
“000”
* Values can be changed by pressing the or keys.
Figure 5—Configuration