beautypg.com

Configuration instructions, Notice – Powers 460 Series AquaSentry 2 Temperature Alarm System User Manual

Page 3

background image

3

1

2

3

4

5

6

7

8

Solenoid (Optional)
Jumper terminals 2 and 6
Connect solenoid to terminals 1 and 8

Sensor Junction Box
Red

Sensor power—Red wire

Yellow Sensor signal—Yellow wire
Black

Sensor return—Black wire

Green

N–C

Module Connections
1

24 VAC

To Transformer

2

24 VAC

3

Sensor return—Black wire

4

Sensor signal—Yellow wire

}

Black

Red

Yellow

Yellow

Black

Red

Transformer
2 wires

Connect to 117 VAC

2 screw terminals

Connect to module

terminals 1 and 2

5

Sensor power—Red wire

6

Relay normally closed

7

Relay normally open

8

Relay common

Figure 3—Wiring for

Gree

n

N/C

Gr

ee

n

N/

C

Dip

Switch

solenoid valve

(solenoid valve supplied

by others)

1. Apply power to the panel. The correct process temperature

should be displayed on the display. If the alarm is sounding,

press the “RESET” key once.

2. Ensure dip switch #2 on the circuit board is in the off position.

(This switch “locks out” the “SET” key if activated.)

3. Press the “SET” key twice to display “HSP” (high setpoint)

value. Use the up or down arrow keys to set the upper setpoint.

4. Press the “SET” key twice to display “LSP” (low setpoint)

value. Use the up or down arrow keys to set the lower setpoint.

If no low alarm is used, set the lower setpoint for 32–35°. (This

will ensure that the alarm will sound if the probe is damaged or

disconnected.)

5. Press the “SET” key three (3) times to return to the operating

mode. Press the “RESET” key if the display is flashing. Unit

should now be fully functional.

6. Position dip switch #2 on the circuit board on the “on” position

to prevent unauthorized configuration changes.

If there is a difference between the reading on the display and the

actual process temperature, note the number of degrees the read-

ing is off. Press the “SET” key 6 times, then enter the different tem-

perature in the CAL setting with the up and down arrow key. Press

the “SET” key one more time to return to the operate mode.

Configuration Instructions

n

NOTICE

1 AC

2 AC

3 GND

4 SEN

5 +5V

6 NC

7 NO

8 COM

BLACK

RED

YELLOW

YELLOW

BLACK

RED

GREEN

N/C

GREEN

N/C

TRANSFORMER

DIP

SWITCH

Figure 4 - Wiring for

Motorized Valve

(Motorized Valve order

separately)

This manual is related to the following products: