Powers ETV400 Emergency Tempering Valves with Internal Cold Water Bypass User Manual
Technical instructions

HydroGuard
®
XP Emergency Tempering valves thermostatically blend hot and cold
water to deliver tepid water to emergency fixtures, quickly compensating for tem-
perature variations due to the changes in inlet temperature or pressure. Powers'
exclusive internal bypass ensures cold water flow in the event of loss of hot water.
US Patent Pending
Description
n
Connections (NPT)
ETV200
.............................................. 3/4" inlets, 1" outlet
ETV400
.............................................. 1-1/4" inlets, 1-1/2" outlet
ETV500
.............................................. 2" inlets, 2" outlet
Maximum Operating Pressure ............................. 125psi (861 kPa)
Maximum Hot Water Temperature . ..................... 180°F (82°C)
Temperature Adjustment Range .......................... 60 - 95°F (15 - 35°C)
Factory Set Temperature* .................................... 85°F (29°C)
Bypass Flow Rate at 30psid*
ETV200
.............................................. 30 gpm (114 lpm)
ETV400
.............................................. 50 gpm (189 lpm)
ETV500
.............................................. 81 gpm (307 lpm)
Maximum Flow with Cold Water Shutoff* .......... 0.5 gpm (1.9 lpm)
Listing ........................................................................ ASSE 1071
* When tested under conditions specified in ASSE 1071 Standard
Specifications
n
HYDROGUARD
®
XP
Emergency Tempering Valve
with Cold Water Bypass
Technical Instructions
Capacity
n
Flow Capacity at 85°F (29.4°C)
P r e s s u r e D r o p A c r o s s V a l v e
Model
Min. Flow
C
V
5psi
10psi
15psi
20psi
30psi
45psi
60psi
to ASSE 1071
(34 kPa)
(69 kPa)
(103 kPa)
(138 kPa)
(207 kPa)
(310 kPa)
(414 kPa)
ETV200
3.0 gpm
6
13.4 gpm
19.0 gpm
23.2 gpm
26.8 gpm
32.9 gpm
40.2 gpm
46.5 gpm
11.4 lpm
50.7 lpm
71.9 lpm
87.8 lpm
101.4 lpm
124.5 lpm
152.2 lpm
176.0 lpm
ETV400
3.0 gpm
15.2
34.0 gpm
48.1 gpm
58.9 gpm
68.0 gpm
83.2 gpm
102.0 gpm
118.0 gpm
11.4 lpm
128.7 lpm
182.0 lpm
223.0 lpm
257.4 lpm
315.0 lpm
386.1 lpm
446.7 lpm
ETV500
3.0 gpm
21.8
48.7 gpm
68.9 gpm
84.4 gpm
97.5 gpm
119.4 gpm
146.2 gpm
168.9 gpm
11.4 lpm
184.3 lpm
260.8 lpm
319.5 lpm
369.1 lpm
452.0 lpm
553.4 lpm
639.4 lpm
IS-P-ETV200_400_500
Advanced Thermal Activation
FAILURE TO COMPLY WITH PROPER INSTALLATION
AND MAINTENANCE INSTRUCTIONS COULD
CONTRIBUTE TO THE VALVE FAILURE, RESULTING IN
INJURY AND DEATH.
TO ENSURE THE ACCURATE AND RELIABLE
OPERATION OF THIS PRODUCT, IT IS ESSENTIAL TO:
• Properly size each valve based on the individual
application.
• Properly design the recirculation system to minimize
pressure and temperature variations.
• Check outlet temperature to ensure it does not
exceed 110°F (43°C). Make sure temperature limit
stop is properly reset to maximum 110°F (43°C) fol-
lowing valve maintenance or repair. Tampering with
limit stop in any way may result in scalding tempera-
ture causing serious bodily harm and/or death.
Periodic Inspection/Maintenance: OPERATION OF
EMERGENCY VALVES AND FIXTURES SHOULD BE
TESTED WEEKLY PER ANSI Z358.1. In addition con-
duct an annual maintenance program by a licensed
plumber or a qualified service technician to ensure
proper operation of the critical components. Regular
checking and cleaning of the thermostat assembly
assures proper product function. Corrosive water
conditions, temperatures over 210°F, unauthorized
adjustments or repair could render the valve ineffec-
tive for the service intended.
WARNING
!
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use
information can result in death, serious personal
injury, property damage, or damage to the
equipment.
Keep this Manual for future reference.